RPc, GPc, XPc, XR Series Installation Instructions IN096 REV F 0823 3 Saber Way, Ward Hill, MA 01835 | radonaway.
Fan Installation & Operating Instructions RPc, GPc, XPc, XR Series Fans Please Read and Save These Instructions. DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS LOCKED IN “OFF” POSITION. DISCONNECT POWER BEFORE SERVICING FAN. 1. WARNING! For General Ventilating Use Only. Do Not Use to Exhaust Hazardous, Corrosive or Explosive Materials, Gases or Vapors. See Vapor Intrusion Application Note #AN001 for important information on VI Applications. RadonAway.
Fan Installation & Operating Instructions RPc Series RP140c RP145c RP260c RP265c GPc Series GP301c GP501c XPc / XR Series XP201c XR261 1.0 SYSTEM DESIGN CONSIDERATIONS 1.1 INTRODUCTION The RPc, GPc, XPc and XR Series Radon Fans are intended for use by trained, professional, certified/licensed radon mitigators. The purpose of these instructions is to provide additional guidance for the most effective use of RPc, GPc, XPc and XR Series Radon Fans.
1.7 CONDENSATION & DRAINAGE Condensation is formed in the piping of a mitigation system when the air in the piping is chilled below its dew point. This can occur at points where the system piping goes through unheated space such as an attic, garage or outside. The system design must provide a means for water to drain back to a slab hole to remove the condensation.
2.0 INSTALLATION The RPc, GPc, XPc and XR Series Radon Fans can be mounted indoors or outdoors. (It is suggested that EPA and radon mitigation standards recommendations be followed in choosing the fan location.) The GPc Radon Fans have an integrated mounting bracket; RPc, XPc and XR Series Radon Fans may be mounted directly on the system piping or fastened to a supporting structure by means of an optional mounting bracket.
THE FOLLOWING CHARTS SHOW THE PERFORMANCE OF THE RPc, GPc, XPc AND XR SERIES RADON FANS RPc Series Product Specifications Typical CFM Vs. Static Pressure “WC Model 0” .2” .5” .75” 1.0” 1.25” 1.5” 1.75” 2.0” RP140c† 138 110* 66* - - - - - RP145c 150* 123* 105 84* 64 44 20 3 RP260c 168 251 210* 157 117 70 26 - - - RP265c 326 290* 241* 207 174* 143 118 89 60 †Energy Star® Rated. *Denotes HVI Certified Values. Model Power Consumption 120VAC, 60Hz, 1.
GPc Series Product Specifications Typical CFM Vs. Static Pressure “WC 1.0” 1.5” 2.0” 2.5” 3.0” 3.5” 4.0” GP301c 64 54 41 4 - - - GP501c - - 66 58 50 27 4 Model Power Consumption 120VAC, 60Hz, 1.5 Amp Maximum Maximum Recommended Operation Pressure* (Sea Level Operation)** GP301c 56-100 watts 2.3” WC GP501c 68 - 146 watts 3.8” WC *Reduce by 10% for High Temperature Operation. **Reduce by 4% per 1000 ft. of altitude. Model Size Weight Inlet/Outlet GP301c 13”H x 12.5” Dia.
IMPORTANT INSTRUCTIONS TO INSTALLER Inspect the RadonAway® RPc, GPc, XPc and XR Series Radon Fan for shipping damage within 15 days of receipt. Notify RadonAway of any damages immediately. RadonAway is not responsible for damages incurred during shipping. However, for your benefit, RadonAway does insure shipments. There are no user serviceable parts inside the fan. Do not attempt to open the housing. Return unit to factory. (See Warranty below).