Instructions / Assembly

!
DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY INSTALLED.
MAKE SURE ELECTRICAL SERVICE TO FAN IS LOCKED IN "OFF" POSITION.
DISCONNECT POWER BEFORE SERVICING FAN.
1.
WARNING!
WARNING! For General Ventilating Use Only. Do Not Use to Exhaust Hazardous, Corrosive or
Explosive Materials, Gases or Vapors. See Vapor Intrusion Application Note #AN001 for important information on VI
applications. RadonAway.com/vapor-intrusion
2.
WARNING!
NOTE: Fan is suitable for use with solid state speed controls however use of speed controls is not
generally recommended.
3.
WARNING!
Check voltage at the fan to insure it corresponds with nameplate.
4.
WARNING!
Normal operation of this device may affect the combustion airflow needed for safe operation of fuel
burning equipment. Check for possible backdraft conditions on all combustion devices after installation.
5.
NOTICE!
There are no user serviceable parts located inside the fan unit.
Do NOT attempt to open. Return unit to the factory for service.
6.
WARNING! Do not leave fan unit installed on system piping without electrical power for more than 48 hours. Fan
failure could result from this non-operational storage.
7.
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a)
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b)
Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the service panel.
c)
Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes
and standards, including fire rated construction.
d)
Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning
equipment to prevent back drafting. Follow the heating equipment manufacturers guideline and safety standards
such as those published by the National Fire Protection Association, and the American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
e)
When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
f)
Ducted fans must always be vented to outdoors.
g)
If this unit is to be installed over a tub or shower, it must be marked as appropriate for the application and be
connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.