Operation Manual

29
Amb. + Limit 2 (external sensor is needed 10k at 25°C)
- The main zone programmer will regulate the temperature in the
room with the internal sensor the external sensor is used as
intelligent floor limiter.
- One new value will be appears:
Floor Offset: 0°C (default value)
Offset added or subtracted to the actual setting ( or )
temperature following by the thermostat, to define the value of the
lower floor limitation.
Important: These two following parameters must be used and
adjusted only by a installer (Please contact your seller, see the last
page for this)
Combined 1 (external sensor is needed 10k at 25°C)
Installation combined with panel heater and floor heating & cooling.
- The main zone programmer will regulate separately the ambient
temperature and floor temperature.
- Two new values will be appears:
Lower limit: 18.0°C (default value)
The floor will never decrease under this value in cooling mode.
Floor setting: 28°C (default value)
Setting point for the floor during the day.
Combined 2 (external sensor is needed 10k at 25°C)
Installation combined with fan coil unit and floor heating & cooling.
- The main zone programmer will regulate separately the ambient
temperature and floor temperature.
- Two new values will be appears:
Lower limit: 18.0°C (default value)
The floor will never decrease under this value in cooling mode.
Floor setting: 28°C (default value)
Setting point for the floor during the day.
4.3.2 Regulation type
In this submenu you must choose the type of regulation which must
be used for the room managed by the programmer.
Regulation type
On / Off
PWM
Panel Heater
Thickness floor >5cm
Thickness floor <5cm