To change the regulation, move the navigation cursor in front of the
desired line and Press (Ok) to valid “”.
On / Off: (Hysteresis)
- Basic regulation with static differential of 0.5°C
PWM: (proportional band)
Panel Heater
- advanced regulation with integral proportional band specially made
for panel heater.
Floor with thickness >5cm
- advanced regulation with integral proportional band specially made
for floor heating with big inertia.
Floor with thickness <5cm
- advanced regulation with integral proportional band specially made
for floor heating with small inertia.
4.3.3 Calibration sensor
In this submenu you can calibrate the sensors.
Procedure for calibration:
- The calibration must be done after 12Hours working with the same
setting temperature.
Ambient sensor calibration:
- To check the temperature in the room, put a thermometer at 1.5M
distance to the floor in the concerned room and wait 1 hour to be
sure that the thermometer show the correct temperature.
Then you can enter the value saw on the thermometer with (-) or
(►+) in the corresponding line “Ambient and press (Ok) to valid.
- When a calibration is made the message “Made” will be displayed.
- To erase the calibration already made press (Ok) and change the
value “made” by “no” with (-) or (►+).
External sensor calibration:
- The calibration must be done same as described above if the
external sensor is connected and used like a deported ambiance
sensor.
- If the external sensor is used as floor sensor, the thermometer
should be put on the floor.
Calibration sensor
Ambient no
Floor (ext) no