Operation Manual

10
10. RF INITIALIZATION (Assign RF Thermostats to zones)
First of all to enter in the parameters menu, press 10 seconds on the (Ok) key, now press once on the (►) key to
display the “rF init” parameter, then press again on the (OK) key to enter in the “rf init mode. The following
message must be appear:
- The number in front of the init text corresponds to the selected zone. (The corresponding LED on the MASTER
RF must be blink in green)
- Use (◄) & (►) keys to change the zone (01 to xx), the green LED blinking cursor move in a same way of the
zone number.
- With (OK) key you can select or de-select the zone(s) which must be learned with a thermostat. The
corresponding LED of the selected zone(s) must be shine in red to indicate that this zone(s) is in wait of thermostat
signal.
1. When you have correctly selected the zones which must be learned with a RF thermostat go to the thermostat
and activate the “rF init” mode. (See the corresponding leaflet of the RF thermostat to do this).
2. Now the thermostat will send the learning message to the MASTER-RF, Check the good reception on the
MASTER-RF display,
- Two squares scrolls on the graphic scope indicate a correct RFsignal.
- The LED previously selected (in RED) must now shine in green to indicate that the zones are correctly
configured with the thermostat.
- You can now switch off the thermostat to avoid perturbation during the installation of the other thermostats.
3. You could now repeat the step 1 to 3 to learn others thermostats. (don’t forgot to switch off the thermostat when
the learning is finished)
4. Only when you have finished the configuration of all thermostats with the MASTER-RF, you could assign the RF
main zone programmer. (See the RF main zone programmer leaflet for this).
5. - When the configuration between MASTER-RF and Main zone programmer RF has finished, the MASTER-
RF should exit the “rF init” mode.
Erase thermostat function:
With this function you could remove one or several thermostats of your installation.
Once on the “RF init menu, choose the zone which must be removed with the blinking cursor and press 5 seconds
in the same time the (+) and (-) keys. Then the LED(s) of the zone(s) which worked with the thermostat will be
removed.