Platform 2:
Icon Step Value Description
1. [TI] Delay
[5s] Place empty
container
Pending for loading an empty container for
the third product (the first product on the 2
weighing platform)
2. [CI] Input
condition
Input 9 „/
Input 9 has to take increasing tendency
press function key confirming loading a
container
3. [T] Tare
Tare
Tarring the weighing platform no. 2
4. [DH] Dose
manually
0,2 kg
[Seasoning]
Manual weighing product “Seasoning”
to obtain 0,2 kg mass
5. [TI] Delay
[5s] Unload
container with
product
Pending for unloading the container with
weighed product from the weighing platform
6. [CI] Input
condition
Input 12 „/”
Input 12 has to take increasing tendency
press function key confirming unloading a
container from the weighing platform
7. [Z] Zero Zero Zeroing the weighing platform no. 2
8. [CF] Flags
condition
Signal flag 1 „1”
Checking condition, whether signal flag 1
is set to value “1” i.e. checking whether
desired part of the process has been already
realized on the weighing platform no. 1. If
Yes, then dosing process on the second
weighing platform shall continue.
9. [O] Outputs
Output 1 „0”,
Output 12 „1”
Output 1 is set to low status the signal for
completing dosing process on the weighing
platfofrm no. 1 is switched off; output 12
takes the high status the main water valve
is opened, for manual dosing of water
ingredient.
10. [DH] Dose
manually
2 kg [Water]
Manual weighing product “Water” to obtain
2kg mass
11. [O]
Outputs
Output 12 „0”
Output 12 is set to low status the main
water valve is closed
12. [TI] Delay
[5s] Unload
container with
product
Pending for unloading the container with
weighed product from the weighing platform
13. [CI] Input
condition
Input 12 „/”
Input 12 can take increasing tendency
press function key confirming unloading a
container from the weighing platform
14. [O]
Outputs
Output 9 „1”
Output 9 is set to high status („1”) signal
confirming carrying out the dosing process
on the weighing platform no. 2 is lit up
15. [TI] Delay
[5s] Dosing
process completed
Displaying a text message on the terminal
confirming completion of dosing process.