13
STPi Controller Operation Manual
Note these additional instructions when connecting a Pump Start Relay:
Master Valve or Pump Start Relay
Step 3
To avoid possible pump damage
when using a Pump Start Relay,
connect a short jumper wire from
any unused zone terminal(s) to
the nearest zone terminal screw
in use.
For example: if you have a 4
Zone Controller with only two
zones in use, route the terminals
for Zones 3 and 4 to the nearest
active terminal (in this example,
Zone 2).
NOTE: Make sure that
!
the total draw of the
Master Valve or Pump
Start Relay, plus the
draw of the valves does
not exceed 0.650 Amps
at 24VAC, 60 Hz.
NOTE: This Controller
!
does not provide main
power for a pump.