Troubleshooting Guide
Featuring Built-In Error Detection
The Timer has a built-in error detection that senses an electrical short circuit or overload
condition on a Zone’s output line.
In the event of an error condition, the following steps take place regarding the
error:
• The aected Zone number and “Err” alert message will show on the display when the
unit is in either AUTO or WATER NOW mode.
• All irrigation for the aected Zone is cancelled and watering advances to the next
operable Zone in the irrigation queue.
Electrical Issues
Problem Possible Cause Possible Solution
Display shows error
message “Err M.” Timer
will not activate zones.
Problem with wiring to Master
Valve (if used). There may be
a break in the wire or a loose
connection.
Check wiring and connections to master valve. Repair or
replace wiring and valve if needed. To clear the ashing
error message, press NEXT.
Display is blank. Power not reaching the Timer. Verify the main AC power supply is securely plugged in
or connected and working properly.
Verify the power supply wires are connected to the
Timer “24 VAC” terminals. (Indoor model.)
Display is frozen and
Timer will not accept
programming.
An electrical surge may have
interfered with the Timer’s
electronics.
Unplug the Timer for 2 minutes, then plug it back in. If
there is no permanent damage, the Timer should accept
programming and resume normal operation.
Press and release the RESET button.
MD
YYYY
NOTE: The Timer will attempt
to water the aected Zone
again at the next scheduled
watering. Completion of a
successful watering will clear
the error condition associated
with that Zone.
ST8 2.0 Timer
Troubleshooting Guide