US English User Manual RAIS X-Basic, RAIS X-Front & RAIS X-Board
Chimney
Flue
Masonry
Insulated
Chimney
Connector Pipe
18” (46cm) below ceiling
Min.
2” (5cm)
Min.
2” (5cm)
For rear venting or other unlisted congura-
tions, consult the local building codes and
follow the NFPA 211 guidelines.
OIf the stovepipe is tted with a bae, it
must be manually operated, visibly placed for
ease of use, and must not close completely.
Consult your chimney expert if you have any
questions.
Important note:
Please ensure that there is easy access to the
chimney cleanout door.
For venting vertically into a Class A chimney, a single
wall pipe (at least 24 gauge) may be used in the room
where the stove is installed. Refer to the manufacturer’s
instructions for the connection to the listed chimney.
The chimney/stove pipe must not be smaller than 8”
(20cm) in diameter.
For venting directly into a masonry chimney or through
a thimble, the top of the single wall pipe must be at
least 18” (46cm) below a combustible ceiling and must
conform to NFPA 211 guidelines and methods. Please
see the diagram to the left.
B.
A.
E.
F.
C.
D.
B.
Required Installation Components:
A. Chimney Cap
B. Insulated Chimney
C. Storm Collar
D. Roof Flashing
E. Ceiling Support Box or Joist Shield/Firestop Spacer
F. Chimney Connector