Specifications
19
Introduction
Trouble Queue Button and Indicator
Flashes yellow when any trouble condition is detected on the panel. The buzzer
sounds at the slow rate.
Pressing the Trouble Queue button allows the user to cycle through and review a
list of active Troubles from oldest to most recent. Once all troubles in the queue
have been reviewed the LED will illuminate steady.
Clearing all Trouble conditions clears the indication and turns the LED off.
Building Queue Button and Indicator
Flashes yellow at the Trouble Flash rate when any Building condition is detected
on the panel. The buzzer sounds at the fast rate.
Pressing the Building Queue button allows the user to cycle through and review a
list of active Building Conditions from oldest to most recent. Once all conditions in
the queue have been reviewed the LED will illuminate steady.
Clearing all Building conditions clears the indication and turns the LED off.
System Reset Button and Indicator
The System Reset button resets the Fire Alarm Control Panel and all Circuits.
Pressing the System Reset button causes a trouble to occur and the LED to
illuminate steady yellow. The following events will occur
• Resets all Latching, Trouble Conditions.
• Resets all Initiating Circuits.
• Resets 4-Wire Smoke Supply and Aux. Power Supply.
• Turns off all Indicating Circuits.
• Turns off Signal Silence, Ack & GA Indicators.
• Turns off Fire Drill.
• Stops and resets all Timers.
• Processes inputs as new events.
• Aux Disconnect is not affected.
• Reset cannot be activated until the Signal Silence Inhibit
timer has expired.
Resetting the System clears the indication and turns the LED off.
Alarm Acknowledge Button and Indicator - Two Stage Operation and
Positive Alarm Sequence
LED and Indicator are active only when the Panel is configured for Two Stage
Operation or Positive Alarm Sequence. Flashes yellow at the Fast Flash Rate as
the Auto General Alarm Timer is timing.
Illuminates steady yellow by pressing the Acknowledge or Signal Silence buttons
and cancelling the Auto General Alarm Timer.
The expiring of the Auto General Alarm Timer causes the Panel to enter General
Alarm, clears the indication and turns the LED off.
Table 11 LED Indicators and Control Buttons (Continued)
LED Indicator and
Control Buttons
Description