MULTI-ZONE DUCTLESS INVERTER SPLIT AIR CONDITIONER WITH HEAT PUMP •INSTALLATION MANUAL• SLIM DUCT TYPE INDOOR UNIT IMPORTANT NOTE: • Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
Table of Contents Installation Manual 1 Accessories . ...................................................04 2 Safety Precautions . ....................................05 3 Installation Overview . ..............................06 4 Indoor Unit Installation . .........................07 ". Indoor Unit Parts ....................................... 07 #. Indoor Unit Installation Instructions. ..... 0 5 Outdoor Unit Installation......................... 18 ". Outdoor Unit Installation Instructions......18 B.
7 Refrigerant Piping Connection . .....................23 A. Notes on Pipe Length and Elevation ............. 23 B. Refrigerant Piping Connection Instructions ..24 L N 8 Wiring. ............................................... 26 ". Outdoor Unit Wiring................... 26 #. Indoor Unit Wiring ...................... 27 $. Power Specifications .................. 28 9 Air Evacuation . ................................................ 30 MC MC ". Evacuation Instructions ................................
1 Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure.
Safety Precautions 2 Read Safety Precautions Cefore Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or B CAUTION. WARNING Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations. Failure to observe a caution may result in injury or equipment damage.
Unit Installation Overview 3 Installation Overview INSTALLATION ORDER 1 3 2 Install the indoor unit (Page 7) 6 Install the outdoor unit (Page 18) 5 MC 4 L N MC Evacuate the refrigeration system (Page 30) 7 Perform a test run (Page 32) Page 6 Install the drainpipe (Page 21) Connect the wires (Page 26) Connect the refrigerant pipes (Page 23)
Indoor Unit Parts Air inlet Electric control cabinet Air filter (on some models) Air outlet Drain hose Refrigerant connecting pipe Fig. 4.1 Safety Precautions CAUTION WARNING • Securely install the indoor unit on a structure that can sustain its weight. If the structure is too weak, the unit may fall causing personal injury, unit and property damage, or even death • DO NOT install the indoor unit in a bathroom or laundry room as excessive moisture can short the unit and corrode the wiring.
Step 2: Hang indoor unit Indoor Unit Installation 1. Please refer to the following diagrams to locate the four positioning screw bolt holes on the ceiling. Be sure to mark the paces where you will drill ceiling hook holes. Air outlet dimensions (Bpplicable to 18-36K series only) Air inlet dimensions Air filter Descending ventilation opening Air filter Electric control box Size of mounted hook Electric control box Fig. 4.
3. Install hanging screw bolts. Cut off the roof beam. Place the wood mounting across the roof beam, then install the hanging screw bolts. (See Fig. 4.4) Strengthen the point at which the cut was made. Consolidate the roof beam. Wood mounting After you select an installation location, align the refrigerant pipes, drain pipes, aOE indoor and outdoor wires with their connection Roof beam points before mounting the unit.
D BC E 345 6 78 9 A Indoor Unit Installation 1 Horsepower code setting Step 3: Duct and accessories installation 1. Install the filter (optional) according to air inlet size. The capacity of the indoor unit has been set 2. Install the canvas tie-in between the body and duct. in the factory according to the UBCMF below 3. The air inlet and air outlet ductT should be far PO WER_S enough apart to avoid BO air passage shortF 0 12 circuit. Horsepower code 4.
Step 6: Fresh air duct installation Dimension: Duct joint for fresh air Indoor Unit Installation Step 5: Adjust the air inlet direction (Grom rear side to under side) 1. Take off UIF ventilation panel and flange, UIFO cut off the staples at UIF side rail. Air return flange MODLE 12-24 Side rail 2. Stick the attached seal sponge JO the indicated place in the following figure, then change the mounting positions of the air return panel and UIF air return flange. Ø90 mm (3.54 JO ) Ø160 mm (6.
Fan performances Static pressure curve (middle static pressure Code 1 Code 0 External sta c pressure in. WG (Pa) 0.08 (20) External sta c pressure in. WG (Pa) 0.06 (15) 0.04 (10) Limit 0.02 (5) Middle High Rated Point Low 0 176 (300) 0.10 (25) 0.08 (20) 0.04 (10) 0.02 (5) 0 235 (400) 294 (500) 353 (600) 412 (700) Limit 0.06 (15) 176 (300) Rated Point Low 235 (400) 294 (500) External sta c pressure in. WG (Pa) External sta c pressure in.
12K Code 1 Code 0 External sta c pressure in. WG (Pa) External sta c pressure in. WG (Pa) 0.06 (15) Limit High 0.04 (10) Rated Point 0.02 (5) Low 0 206 (350) Indoor Unit Installation 0.10 (25) 0.08 (20) 265 (450) 324 (550) 382 (650) 0.08 (20) Limit Rated Point 0.04 (10) Middle 0.02 (5) 0 441 (750) High 0.06 (15) 206 (350) Low 265 (450) 0.20 (50) 0.14 (35) 0.12 (30) Limit External sta c pressure in. WG (Pa) External sta c pressure in.
18K Code 1 High Rated Point External sta c pressure in. WG (Pa) 0.16 (40) 0.14 (35) 0.12 (30) Limit 0.10 (25) 0.08 (20) 0.06 (15) 0.04 (10) 0.02 Low (5) 0 176 235 294 353 (300) (400) (500) (600) 0.20 (50) Limit Rated Point 0.12 (30) 0.08 (20) Low 176 235 294 353 (300) (400) (500) (600) 412 471 529 588 647 (700) (800) (900) (1000) (1100) Code 4 0.32 (80) High Limit 0.16 (40) 0.12 (30) 0.08 (20) 0.
24K Code 1 Code 0 External sta c pressure in. WG (Pa) External sta c pressure in. WG (Pa) 0.16 (40) High Limit 0.12 (30) Middle 0.08 (20) Rated Point 0.04 (10) 0 353 (600) Low 471 (800) 588 (1000) 706 (1200) 824 (1400) 0.20 (50) High Limit 0.16 (40) Middle Rated Point 0.12 (30) 0.08 (20) 0.04 (10) 0 353 (600) 941 (1600) Low 471 (800) Code 2 High Limit Middle Rated Point 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10) 0 353 (600) External sta c pressure in.
36K Code 1 Code 0 0.28 (70) 0.24 (60) Limit High 0.20 (50) 0.16 (40) Middle 0.12 (30) Rated Point 0.08 (20) 0.04 (10) Low External sta c pressure in. WG (Pa) External sta c pressure in. WG (Pa) 0.24 (60) 0 Limit 0.20 (50) Middle Rated Point 0.16 (40) 0.12 (30) 0.08 (20) Low 0.
48K Code 0 Code 1 High Limit 0.16 (40) Middle 0.12 (30) 0.08 (20) 0.04 (10) Low External sta c pressure in. WG (Pa) External sta c pressure in. WG (Pa) 0.20 (50) Low Air volume CFM (m3/h) Code 3 External sta c pressure in. WG (Pa) Code 2 External sta c pressure in.
5 Outdoor Unit Installation Outdoor Unit Installation Instructions Outdoor Unit Installation Step 1: Select installation location. The outdoor unit should be installed in the location that meets the following requirements: √ Place the outdoor unit as close to the indoor unit as possible. √ Ensure that there is enough room for installation and maintenance. √ The air inlet and outlet must not be obstructed or exposed to strong wind.
Split Type Outdoor Unit (Refer to Fig 5.4, 5.5, 5.6, BOE 5.10 and Table 5.1) Vertical Discharge Type Outdoor Unit (Refer to Fig 5.7, 5.8, BOE 5.9 and Table 5.2) (Wall or obstacle) Air Putlet H >120 cm/47 JO Fig. 5.4 Fig. 5.7 W Outdoor Unit Installation W H W H Fig. 5.5 D Fig. 5.8 A (Wall or obstacle) > 30 cm / 11.8 JO D B Fig. 5.6 > 30cm/11.8 JO Air inlet Distance B 760x590x285 (29.9x23.2x11.2) 530 (20.85) 290 (11.4) 810x558x310 (31.9x22x12.2) 549 (21.6) 325 (12.
Outdoor Unit Installation 60 cm/23.6 JO above NOTE: The minimum distance between the outdoor unit and UIF walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 5.10) 30 c m/11 .8 JO M ck JO .8 30 11 m/ m fro ba ll wa c on le ft 60 cm /23.
6 Drainpipe Installation The drainpipe is used to drain water away from the unit. Improper installation may cause unit and property damage. CAUTION NOTE ON PURCHASING PIPES Installation requires a polyethylene tube (exterior diameter = 3.7 - 3.9 cm, interior diameter = 3.2 cm), which can be obtained at your local hardware store or dealer. Drainpipe installation for units with a pump Ceiling < 20 cm (7.9 JO) < 55 cm (21.
3. Using a 65 mm (2.5 JO) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 12 mm (0.5 JO). This will ensure proper water drainage (See Fig. 6.5). Place the protective wall cuff in the hole. This XJMM protect the edges of the hole and will help seal it once you finish installation. Units with a pump 1. Remove the test cover. Fill the water pan with 2 liters of water.
7 Refrigerant Piping Connection Notes Pn Pipe Length and Elevation Safety Precautions WARNING Table 7.1: The Maximum Length And Drop Height Based on Models. (Unit: m/ft.) Type of model North America, Australia and the eu frequency conversion Split Type Other Split Type Capacity (Btu/h) <15K Length of piping Maximum drop height 25/82 10/32.8 15K - <24K 30/98.4 20/65.6 24K - <36K 50/164 25/82 36K - 60K 65/213 30/98.4 12K 15/49 8/26 18K-24K 25/82 15/49 30K-36K 30/98.4 20/65.
Table 7.2 CAUTION Permitted length Total piping length 18K+18K 30m/98 GU 24K+24K 50m/164 GU L+Max (L1, L2) 30K+30K Piping length Drop height (farthest distance from the line pipe branch) 15m/49 GU L1, L2 (farthest distance from the line pipe branch) 10m/32.8 GU L1-L2 Drop height between indoor and outdoor unit 20m/65.6 GU H1 Drop height between two indoor units 0.5m/1.6 GU H2 DO NOT deform UIF pipe while cutting. Be FTQFDJBMMZ careful not to damage PS dent the pipe.
5. Clamp UIF flare form on the end of the pipe. NOTE: Use both a spanner and a torque wrench The end of the pipe must extend beyond when connecting or disconnecting pipes to/from the flare form. the unit. Flare form Fig. 7.8 Pipe Fig. 7.5 Place UIF flaring tool onto the form. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in 5able 7.5. Table 7.
8 Wiring Safety Precautions WARNING Wiring • Disconnect the power supply before working on the unit. • All wiring must be performed according to local and national regulations. • Wiring must be done by a qualified technician. Improper connections may cause electrical malfunction, injury, or fire. • An independent circuit and single outlet must be used for this unit. DO NOT plug another appliance or charger into the same outlet.
Table 8.2: Other World Regions Rated Current of Nominal Cross-Sectional Appliance (A) Area (mm²) 6 0.75 1 1.5 2.5 4 6 6 - 10 10 - 16 16 - 25 25 - 32 32 - 45 C Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal approximately 15 cm (5.9 JO) of wire. D Strip the insulation from the ends. E Using a wire crimper, crimp u-lugs on the ends. NOTE: When connecting the wires, strictly follow the wiring diagram found inside the electrical box cover. 2.
Power Specifications NOTE: Electric auxiliary heating type circuit breaker/fuse needT to add more than 10 A.
36K MODEL (Btu/h) 1 Phase PHASE FREQUENCY 208-240V AND VOLT 15/10 CIRCUIT BREAKER/FUSE(A) PHASE 3 Phase POWER (outdoor) FREQUENCY 380-420V AND VOLT CIRCUIT BREAKER/FUSE (A) 25/20 POWER (indoor) 37K 60K 36K 37K 60K 1 Phase 1 Phase 1 Phase 208-240V 208-240V 208-240V 15/10 3 Phase 15/10 3 Phase 15/10 3 Phase 380-420V 208-240V 208-240V 32/25 32/25 45/35 Inverter Type A/C Power Specifications MODEL (Btu/h) 18K 19K 24K 25K 36K 37K 48K 49K 60K 1 Phase 1 Phase 1 Phase PHASE FREQUENCY 220-24
9 Air Evacuation Safety Precautions CAUTION • Use a vacuum pump with a gauge reading lower than -0.1MPa and an air discharge capacity above 40 L/min. • The outdoor unit does not need to be vacuumed. DO NOT open the outdoor unit’s gas and liquid stop valves. • Ensure that the Dompound Neter reads -0.1MPa or below after 2 hours. If after hours the gauge reading is still above -0.1MPa, check if there is a gas leak or water inside the pipe. If there is no leak, perform another evacuation for 1 or 2 hours.
Note Pn Adding Refrigerant CAUTION • Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. • DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact it’s functionality. • Charging with unsuitable substances may cause explosions or accidents. Ensure that the appropriate refrigerant is used. • Refrigerant containers must be opened slowly. Always use protective gear when charging the system.
Test Run Before Test Run A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test: B Indoor and outdoor units are properly installed. C Piping and wiring are properly connected. D No obstacles BSF near the inlet and outlet of the unit that might cause poor performance or product malfunction. E Refrigeration system does not leak. F Drainage system is unimpeded and drainT to a safe location.
The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details.
MULTI-ZONE DUCTLESS INVERTER SPLIT AIR CONDITIONER WITH HEAT PUMP »USER’S MANUAL« SLIM DUCT TYPE INDOOR UNIT IMPORTANT NOTE: • Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
Table of Contents Owner’s Manual 1 Safety Precautions .................................................... 04 SAFETY FIRST 2 Indoor Unit Parts and Major Functions 3 Manual Operations.................................................... ..........
4 Care and Maintenance ............................. a. Unit Maintenance ....................................... b. How to Clean the Air Filter ....................... c. Repairing Refrigerant Leaks ...................... d. Preparation for Periods of Non-use ........ 5 Troubleshooting ................................. a. Common Problems ............................ b. Troubleshooting Tips .........................
Safety General Precautions Introduction 1 Safety Precautions Thank you for purchasing this air conditioner. This manual will provide you with information on how to operate, maintain, and troubleshoot your air conditioner. Following the instructions will ensure the proper function and extended lifespan of your unit. Please pay attention to the following signs: WARNING Failure to observe a warning may result in death. The appliance must be . installed in accordance with national regulations.
Unit Parts Air inlet Electric control cabinet Air filter(on some models) Air outlet Drain hose Refrigerant connecting pipe Fig. 2.1 Operating Conditions Use the system under the following temperatures for safe and effective operation. If the air conditioner is used under different conditions, it may malfunction or become less efficient.
Features Indoor Unit Parts And Major Functions Default Setting Louver Angle Memory Function (Optional) When the air conditioner restarts after a power failure, it will default to the factory settings (AUTO mode, AUTO fan, 24°C (76°F)). This may cause inconsistencies on the remote control and unit panel. Use your remote control to update the status. Some models are designed with a louver angle memory function.
3 Manual Operations This display panel on the indoor unit can be used to operate the unit in case the remote control has been misplaced or is out of batteries. Manual Operations LED display Manual button Operation indicator Timer indicator Infrared receiver Alarm indicator PRE-DEF (pre-heating/defrost) indicator Fig. 3.1 • MANUAL button: This button selects the mode in the following order: AUTO, FORCED COOL, OFF. • FORCED COOL mode: In FORCED COOL mode, the Operation light flashes.
4 Care And Maintenance Safety Precautions Contact an authorized service technician for repair or maintenance. Improper repair and maintenance may cause water leakage, electrical shock, or fire, and may void your warranty. • DO NOT substitute a blown fuse with a higher or lower amperage rating fuse, as this may cause circuit damage or an electrical fire. • Make sure the drain hose is set up according to the instructions.
3. Remove the air filter. 4. Clean the air filter by vacuuming the surface or washing it in warm water with mild detergent. Repairing Refrigerant Leaks WARNING A. If using a vacuum cleaner, the inlet side should face the vacuum. If the refrigerant leaks, turn off the air conditioner and any combustible heating devices, ventilate the room and call your dealer immediately. Refrigerant is both toxic and flammable. DO NOT use the air conditioner until the leak is repaired.
5 Troubleshooting CAUTIONS If one of the following conditions occurs, switch off the power supply immediately and contact your dealer for further assistance. • • • • • The operation light continues to flash rapidly after the unit has been restarted. The remote control buttons do not work. The unit continually trips fuses or circuit breakers. A foreign object or water enters the air conditioner. Other abnormal situations.
Problem Possible Causes Dust is emitted from either the indoor or outdoor unit The unit emits a bad odor The fan of the outdoor unit does not operate The unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is turned on. This can be mitigated by covering the unit during long periods of inactivity. The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
Error Codes Cause Number The number of flashes per second Timer indicator Error Code Troubleshooting 1 Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error 1 Off E0 2 Indoor and outdoor unit communication malfunction 2 Off 3 Indoor fan speed malfunction 4 Off 4 Indoor room temperature sensor error 5 Off 5 Evaporator coil temperature sensor error 6 Off 6 Refrigerant leak detection system malfunction 7 Off 7 Water level alarm malfunction 8 Off 8 9 Off