MULTI-ZONE DUCTLESS INVERTER SPLIT AIR CONDITIONER WITH HEAT PUMP •INSTALLATION MANUAL• CASSETTE TYPE INDOOR UNIT IMPORTANT NOTE: • Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
CONTENTS Install strictly according to these installation instructions. If installation is defective, water leakage, electrical shock, and fire will result. Page PRECAUTIONS ...................................................................................1 INSTALLATION INFORMATION ..........................................................
When there are inflammable materials or gas nearby If the refrigerant leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant comes into contact with fire. When acid or alkaline liquid is evaporating When other special conditions exist The temperature of the refrigerant circuit will be high, so keep the interconnection cable away from the copper tube. The appliance must be installed in accordance with national wiring regulations.
ACCESSORIES For the following items, take special care during construction and check after installation is finished. Ensure that the following accessories are included with your unit: 2 1 1x 3 1x 2x Mark√ when finished 4 2x Is the indoor unit fixed firmly? The unit may drop, vibrate, or make noise. Is the gas leak test finished? It may result in insufficient cooling or heating. 7 6 5 1x 1x+1x 1x Is the unit fully insulated? Condensate water may drip.
When the conditions in the ceiling exceed 300 C/860 F and a relative humidity of 80%, or when fresh air is inducted into the ceiling, an additional insulation is required (min. 10 mm/0.4 in thickness, polyethylene foam). 1000/39.4 in - 1000/39.4 in Optimum air distribution can be ensured. Nothing blocks air passage. Condensate water can be properly drained. The false ceiling is not on a noticeable incline. There is sufficient clearance for maintenance and service.
1.2 1 2 Where applicable, create the ceiling opening that is necessary for installation (for existing ceilings) - From the side of the opening to the casing outlet, implement the refrigerant and drain piping and wiring for the remote control (unnecessary for the wireless type). Refer to each piping or wiring section. - After making an opening in the ceiling, you may need to reinforce the ceiling beams to maintain the ceiling level and to prevent it from vibrating. Consult the builder for details.
1.3 4) Check if the unit is horizontally level Install the indoor unit - Do not install the unit tilted. The indoor unit is equipped with a built-in drain pump and float switch. (If the unit is tilted against the direction of the condensate flow (the drain piping side is raised), the float switch may malfunction and cause water to drip. - With a water level or water-filled vinyl tube, check if the unit is level at all four corners, as shown in the figure below.
OUTDOOR UNIT INSTALLATION 2.1 Precautions for selecting the location 1) Choose a place solid enough to bear the weight and vibration of the unit, where operation noise will not be amplified. 2) Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors. 3) To lessen the irritation of the operation noise, avoid placing the unit near bedrooms and the like. 4) There must be sufficient space for carrying the unit into and out of the site.
2.4 Outdoor unit installation 2.3 Installation guidelines When a wall or other obstacle is in the path of the outdoor unit inlet or outlet airflow, follow the installation guidelines below. 1) Installing the outdoor unit When installing the outdoor unit, refer to "Precautions for selecting the location." For any of the below installation patterns, the wall height on the outlet side should be 1200 mm (47.2 in) or less.
3 INSTALLING THE REFRIGERANT PIPE 3.1 Flaring the pipe end 1) Cut the pipe end with a pipe cutter. All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes. 2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe. Precautions Cut exactly at right angles Execute heat insulation work completely on both sides of the gas piping and liquid piping. Otherwise, water leakage may result.
3.4 Purging air and checking gas leakage 3.3 Installation of the throttle (for some models) ≥5 /19 00mm When piping work is completed, purge the air and check for gas leakage. .7in WARNING Do not mix any substance other than the specified refrigerant into the refrigeration cycle. When refrigerant gas leaks, ventilate the room as soon as possible. The specified refrigerant should always be recovered and should never be released directly into the environment.
Pipe length Up to 15 m (49.2 ft) More than 15 m (49.2 ft) Run time Not less than 10 min Not less than 15 min 2) Be sure to insulate both the gas and liquid piping. Use separate thermal insulation for each. See the figure below. *2. If the compound pressure gauge pointer swings back, the refrigerant may contain water content or a pipe joint may be loose. Check all pipe joints and retighten nuts as needed, then repeat steps 2 through 4. Inter-unit wire Gas pipe 3.
4 CONNECTING THE DRAIN PIPE 4.3 How to perform piping 4.1 Installation of drain piping 1 5 3 6 5 1 4 ≤750/29.5in 2 220/8.7in ≤530/20.9in 1-1.5 m 3-5 ft ≤300/11.8in 0~75 0~3 in Install the drain piping as shown in the figure below and take measures against condensation. Improperly rigged piping could lead to leaks and, eventually, wet furniture and belongings. 1-1.
4.4 Testing of drain piping 5 After the piping work is finished, check if drainage flows smoothy. General instructions Gradually add approximately 1 L of water through the air discharge outlet. See the figure below for how to add water. All field wiring and components must be installed by a licensed electrician and must comply with relevant European and national regulations. 106/4.2 in 65/2.6 in ≥100/3.9in Use copper wire only.
How to connect wiring Remove the control box lid of the indoor unit. Remove the cover of the outdoor unit. Follow the "Wiring diagram label" attached to the indoor unit's control box lid to wire the outdoor unit, indoor unit, and remote control. Securely fix the wires with a field-supplied clamp. Attach the cover of the outdoor unit.
6 INSTALLATION OF THE DECORATION PANEL - After installing the decoration panel, ensure that there is no space between the unit body and the decoration panel. If there is, air may leak through the gap and cause dewdrop. (See the figure below.) Detach the intake grille - Slide the 2 grille hooks toward the middle of the decoration panel. 1 × √ 2 Mount the intake grille 1 2 Intake grille Grille hook Ensure that the buckles at the back of the grille are properly seated in the groove of the panel.
Close the intake grille and the 2 grille hooks 7 TEST OPERATION Make sure the control box lids are closed on the indoor and outdoor units. Refer to ''For the following items, take special care during construction and check after installation is finished'' on page 3. After finishing the construction of the refrigerant piping, drain piping, and electric wiring, conduct the test operation accordingly to protect the unit. Test operation after installing the decoration panel. 1 Open the gas side stop valve.
The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details.
MULTI-ZONE DUCTLESS INVERTER SPLIT AIR CONDITIONER WITH HEAT PUMP »USER’S MANUAL« CASSETTE TYPE INDOOR UNIT IMPORTANT NOTE: • Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
CONTENT IMPORTANT SAFETY INFORMATION---------------------------------------------------------------------1 HINTS FOR ECONOMICAL OPERATION-----------------------------------------------------------------2 PARTS NAMES----------------------------------------------------------------------------------------------------2 MANUAL OPERATION-----------------------------------------------------------------------------------------14 ADJUSTING AIR FLOW DIRECTION-----------------------------------------------------------
IMPORTANT SAFETY INFORMATION Danger CAUTION Do not attempt to install this unit before reading its documentation entirely. There are specific procedures and steps to follow. DANGER Do not attempt to service the unit yourself. This unit has no user serviceable components. Opening or removing the cover will expose you to dangerous voltage. Tuning off the power supply will not prevent potential electric shock. DANGER Never put hands or objects into the Air Outlet of indoor or outdoor units.
HINTS FOR ECONOMICAL OPERATION The following should be noticed to ensure an economical operation. (Refer to corresponding chapter for details) Adjust the air flow direction properly to avoid winding toward your body. Adjust the room temperature properly to get a comfortable situation and to avoid supercooling and superheat. In cooling, close the curtains to avoid direct sunlight. To keep cool or warm air in the room, never open doors or windows more often than necessary.
NAMES AND FUNCTIONS a) indoor unit b) outdoor unit c) remote controller d) air-in e) air-out f ) air outlet g) air flow louver (at air outlet) h) connecting pipe i ) drain hose j ) air inlet (with air filter in it) k) drain pump (drain water from indoor unit) l ) infrared signal receiver m) temporary button n) operation lamp o) timer indicator p) PRE-DEF indicator (cooling and heating type) or fan only indicator (cooling only type) q) alarm indicator High-static Pressure Parvis Split Type k l f a g m
Duct and Ceiling Type f i k l h a m d g j n p o b e d c or e b d NOTICE! This chart is based on 24000Btu/h type. So, a few differences may exist on the outlook and functions from yours.
For Slim Duct Type f k l a h m n g p o Display Panel b j i d e b 温度 时钟 风速 自动 模 式 or 开 风 速 关 温 度 e c d NOTICE! This chart is based on 24000Btu/h. type. So, a few differences may exist on the outlook and functions from yours. NAMES AND FUNCTIONS a indoor unit d air-inlet outdoor unit c remote controller air-out f air- outlet h g connecting pipe i drain hose b e j E-Box k infrared signal receiver l temporary button m operation lamp o PRE./DEF.
For Slim DUCT with air inlet box Type k l f a g m n d p o Display Panel b f j d i e b h 温度 时钟 风速 自动 模 式 or 开 风 速 关 温 度 e c d NAMES AND FUNCTIONS a indoor unit d g j E-Box k infrared signal receiver l temporary button m operation lamp o PRE./DEF.
Four-way Cassette(slim) Type 11 10 Control board 12 11 10 13 10 14 15 11 Indoor Unit Assy 1 12 6 5 Manual SET OPERATION TIMER DEF./FAN. ALARM OPERATION TIMER DEF./FAN. ALARM 9 4 8 13 14 15 12 13 14 15 NOTE: These three indication lamps flash in cycles when solar PV ECO function is activated.(Applicable to the unit adopts solar photovoltaic system only.
One-way Cassette Type INDOOR UNIT INDOOR UNIT Outlet louver Inlet Filter MANUAL RUN FAN TIMER ALARM Display panel Remote controller TEMP CLOCK C SPEED MODE I FAN O TEMP OUTDOOR UNIT OUTDOOR UNIT Refrigerant connecting, drain hose pipe inlet Electric wiring Trap inlet Air outlet Air inlet(side and rear) outlet DISPLAY PANEL Display panel MANUAL button MANUAL Run lamp MANUAL FAN indicator(Cooling/Heating RUN TIMER DEF ALARM RUN TIMER FAN ALARM type without) TIMER indicator ALARM indic
Ceiling & Floor Type (for VERTICAL DISCHARGE AIR CONDITIONER) l m J g n i a e o f k Display Panel p h d d b p b or d p c NOTICE! The chart based on one model of our product is for reference only, which may be different from the unit you purchased. NAMES AND FUNCTIONS a indoor unit d g i installation part j FAN/DEF indicator (For cooling and heating type, it s DEF.
Ceiling & Floor Type g q i a J n k l m o e f Display Panel p h d d b p b or d p c NOTICE! The chart based on one model of our product is for reference only, which may be different from the unit you purchased. NAMES AND FUNCTIONS a indoor unit d g i installation part j FAN/DEF indicator (For cooling and heating type, it s DEF.
Ceiling & Floor Type g o k l i a m j q n e MANUAL OPERATION TIMER DEF./FAN ALARM f Display Panel p h d d b p b or d p c NOTICE! The chart based on one model of our product is for reference only, which may be different from the unit you purchased. NAMES AND FUNCTIONS a indoor unit d g i installation part j FAN/DEF indicator (For cooling and heating type, it s DEF.
Ceiling & Floor Type i a k g e f n o j m l Display Panel p h d d b p b or d p c NOTICE! The chart based on one model of our product is for reference only, which may be different from the unit you purchased. NAMES AND FUNCTIONS a indoor unit d g i installation part j FAN/DEF indicator (For cooling and heating type, it s DEF.
Ceiling & Floor Type R Q i a I K J M n O g e f Display Panel p h d d b p b or d p c NOTICE! The chart based on one model of our product is for reference only, which may be different from the unit you purchased. NAMES AND FUNCTIONS a indoor unit d g i installation part j FAN/DEF indicator (For cooling and heating type, it s DEF.
MANUAL OPERATION Ceiling & Floor This function is used to operate the unit temporarily in case you misplace the remote controller or its batteries are exhausted. Two modes including AUTO and FORCED COOL can be selected through the TEMPORARY BUTTON on the air-in grill control box of the indoor unit. Once you push this button, the air conditioner will run in such order: AUTO, FORCED COOL, OFF, and back to AUTO. 1 AUTO The OPERATION lamp is lit, and the air conditioner will run under AUTO mode.
ADJUSTING AIR FLOW DIRECTION Cassette Type While the unit is in operation, you can adjust the air flow louver to change the flow direction and naturalize the room temperature evenly. Thus you can enjoy it more comfortably. 1. Set the desired air flow direction. Push the SWING button to adjust the louver to the desired position and push this button again to maintain the louver at this position. 2. Adjust the air flow direction automatically. Push the SWING button, the louver will swing automatically.
MAINTENANCE ! WARNING WARNING Before you clean the air conditioner, be sure to disconnect the power supply plug. Cleaning the indoor unit and remote controller ! CAUTIONS Use a dry cloth to wipe the indoor unit and remote controller. A cloth dampened with cold water may be used on the indoor unit if it is very dirty. Never use a damp cloth on the remote controller.
Cassette Type 1. Open the air-in grill Push the grill switches towards the middle simultaneously as indicated in sketch A. Then pull down the air-in grill. Cautions: The control box cables ,which are originally connected with the main body electrical terminators must be pulled off before doing as indicated above. A B 2. Take out the air-in grill (together with the air filter shown in Sketch B) Pull the air-in grill down at 45 o and lift it up to take out the grill. 3. Dismantle the air filter 4.
4. Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy , please use soft brush and mild detergent to clean it and dry out in cool place) . Fig. 1 Fig. 2 The air-in side should face up when using vacuum cleaner. (See Fig. 1) The air-in side should face down when using water. (See Fig. 2) Cautions : Do not dry out the air filter under direct sunshine or with fire. 5. Re-install the air filter 6.
Special functions Refrigerant Leakage Detection(optional): With this new technology, the dipsplay area will appear EC (if applicable) and the LED indication lamps continue flashing when the outdoor unit detects refrigerant leakage. Louver Angle Memory Function(optional): For some models, the machine is special designed with louver angle memory function. Power failure during operation or pressing the ON/OFF button on the remote controller will stop the unit completely.
TROUBLES AND CAUSES Before you ask for servicing or repairs, check the following points. Recheck Inoperative The power fuse is blown or the circuit breaker has been tripped. The batteries in the remote controller are exhausted. The timer is set. Does not cool or heat well. The air inlet or outlet of the outdoor unit is blocked. Doors or windows are open. The air filter is clogged with dust. The louver is not at the correct position. The fan speed is set to low.
The Transmission Indicator " " Never Comes On Symptoms Reason and Disposal Causes The remote control signal is not transmitted even when the ON/OFF button is pushed. Check whether the batteries in the remote controller are exhausted. The remote control signal is not transmitted, because the power supply is off. The Display Never Comes On Symptoms Reason Causes Check whether the MODE indicated on the display is "FAN ONLY". FAN ONLY The TEMP. indicator does not come on.
The following displays indicate an error or problem: NO Malfunction Display (nixie tube) timer lamp running lamp (flashes per second) E0. OFF 1 Communication malfunction between indoor and outdoor units E1. OFF 2 3 Indoor fan speed malfunction E3. OFF 4 4 Indoor room temperature sensor open circuit or short circuit E4. OFF 5 5 Evaporator coil temperature sensor open circuit or short circuit E5. OFF 6 6 Refrigerant leakage detection malfunction EC.