Chapter 7: Using the Command Line Interface
149
Displayed information:
Without the parameter "details," only the inlet's L1, L2 and L3 current
values and inlet name are displayed.
With the parameter "details," more inlet information is displayed in
addition to the RMS current values, such as the inlet's RMS current,
voltage, and active power.
Inlet Pole Sensor Information
This command is available only for a three-phase PDU except for an
inline monitor.
This command syntax shows the specified inlet pole sensor's information.
# show sensor inletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of the
command.
# show sensor inletpole <n> <p> <sensor type> details
Variables:
<n> is the number of the inlet whose pole sensors you want to query.
<p> is the label of the inlet pole whose sensors you want to query.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2
2
L2
L2 L2 - L3
3
L3
L3 L3 - L1
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor