User guide
Chapter 7: Using the Command Line Interface
160
Example
The following command enables the data logging feature.
config:# pdu dataRetrieval enable
Setting the Data Logging Measurements Per Entry
This command syntax defines the number of measurements accumulated
per log entry.
config:# pdu measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60 samples
per log entry.
For more information, see Setting Data Logging (on page 62).
Example
The following command determines that 66 measurements are
accumulated per log entry for internal sensors, that is, 66 seconds.
config:# pdu measurementsPerLogEntry 66
Setting the Z Coordinate Format for Environmental Sensors
This command syntax enables or disables the use of rack units for
specifying the height (Z coordinate) of environmental sensors.
config:# pdu externalSensorsZCoordinateFormat <option>
Variables:
<option> is one of the options: rackUnits or freeForm.
Option Description
rackUnits The height of the Z coordinate is measured in
standard rack units. When this is selected, you can
type a numeric value in the rack unit to describe
the Z coordinate of any environmental sensors.
freeForm
A
ny alphanumeric string can be used for specifying
the Z coordinate.