User guide

Chapter 7: Using the Command Line Interface
184
Sensor type Description
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the upper warning threshold for the
specified inlet sensor.
disable Disables the upper warning threshold for the
specified inlet sensor.
A numeric value Sets a value for the upper warning threshold of the
specified inlet sensor without enabling or disabling
the threshold.
Example
The following command sets the Upper Warning threshold for the inlet 1
RMS current to 27A.
config:# sensor inlet 1 current upperWarning 27
Setting the Inlet's Lower Critical Threshold
This command syntax configures the Lower Critical threshold of an inlet.
config:# sensor inlet <n> <sensor type> lowerCritical <option>
Variables:
<n> is the number of the inlet that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor
activeEnergy Active energy sensor