User guide

Chapter 7: Using the Command Line Interface
186
Sensor type Description
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the lower warning threshold for the
specified inlet sensor.
disable Disables the lower warning threshold for the
specified inlet sensor.
A numeric value Sets a value for the lower warning threshold of the
specified inlet sensor without enabling or disabling
the threshold.
Example
The following command sets the Lower Warning threshold for the inlet 1
RMS current to 20A.
config:# sensor inlet 1 current lowerWarning 20
Setting the Inlet's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of an
inlet.
config:# sensor inlet <n> <sensor type> hysteresis <value>
Variables:
<n> is the number of the inlet that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor