User guide

Chapter 7: Using the Command Line Interface
187
Sensor type Description
activeEnergy Active energy sensor
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<value> is a numeric value that is assigned to the hysteresis for the
specified inlet sensor. See What is Deassertion Hysteresis? (on
page 100) for how the deassertion hysteresis works.
Example
The following command sets the deassertion hysteresis for the inlet 1
RMS current to 0.3A.
config:# sensor inlet 1 current hysteresis 0.3
Commands for Inlet Pole Sensors
A sensor configuration command for inlet poles begins with sensor
inletpole.
Setting the Upper Critical Threshold for an Inlet Pole
This command syntax configures the Upper Critical threshold of an inlet
pole.
config:# sensor inletpole <n> <p> <sensor type> upperCritical <option>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2
2
L2
L2 L2 - L3
3
L3
L3 L3 - L1
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor