User guide
Chapter 7: Using the Command Line Interface
188
Sensor type Description
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor
activeEnergy Active energy sensor
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the upper critical threshold for the
specified inlet pole sensor.
disable Disables the upper critical threshold for the
specified inlet pole sensor.
A numeric value Sets a value for the upper critical threshold of the
specified inlet pole sensor without enabling or
disabling the threshold.
Example
The following command disables the Upper Critical threshold for the pole 3
(L3-L1) voltage of the inlet 1.
config:# sensor inletpole 1 L3 voltage upperCritical disable
Setting the Upper Warning Threshold for an Inlet Pole
This command syntax configures the Upper Warning threshold of an inlet
pole.