Example
The following command sets the Upper Warning threshold for the pole 2
(L2-L3) voltage of the inlet 1 to 180V.
config:# sensor inletpole 1 L2 voltage upperWarning 180
Setting the Lower Critical Threshold for an Inlet Pole
This command syntax configures the Lower Critical threshold of an inlet
pole.
config:# sensor inletpole <n> <p> <sensor type> lowerCritical <option>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2
2
L2
L2 L2 - L3
3
L3
L3 L3 - L1
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor
activeEnergy Active energy sensor
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.