User guide

Chapter 7: Using the Command Line Interface
191
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the lower critical threshold for the
specified inlet pole sensor.
disable Disables the lower critical threshold for the
specified inlet pole sensor.
A numeric value Sets a value for the lower critical threshold of the
specified inlet pole sensor without enabling or
disabling the threshold.
Example
The following command enables the Lower Critical threshold for the pole 2
(L2-L3) voltage of the inlet 1.
config:# sensor inletpole 1 L2 voltage lowerCritical enable
Setting the Lower Warning Threshold for an Inlet Pole
This command syntax configures the Lower Warning threshold of an inlet
pole.
config:# sensor inletpole <n> <p> <sensor type> lowerWarning <option>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2
2
L2
L2 L2 - L3
3
L3
L3 L3 - L1
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor