User guide

Chapter 7: Using the Command Line Interface
192
Sensor type Description
apparentPower Apparent power sensor
powerFactor Power factor sensor
activeEnergy Active energy sensor
unbalancedCurrent Unbalanced current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the lower warning threshold for the
specified inlet pole sensor.
disable Disables the lower warning threshold for the
specified inlet pole sensor.
A numeric value Sets a value for the lower warning threshold of the
specified inlet pole sensor without enabling or
disabling the threshold.
Example
The following command sets the Lower Warning threshold for the pole 3
(L3-L1) voltage of the inlet 1 to 190V.
config:# sensor inletpole 1 L3 voltage lowerWarning 190
Setting the Inlet Pole's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of an
inlet pole.
config:# sensor inletpole <n> <p> <sensor type> hysteresis <value>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2