User guide
Chapter 7: Using the Command Line Interface
198
Setting the Circuit Breaker's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of a
circuit breaker.
config:# sensor ocp <n> <sensor type> hysteresis <value>
Variables:
<n> is the number of the circuit breaker that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
Note: If the requested sensor type is not supported, the message
"Sensor is not available" is displayed.
<value> is a numeric value that is assigned to the hysteresis for the
specified circuit breaker sensor. See What is Deassertion
Hysteresis? (on page 100) for how the deassertion hysteresis works.
Example
The following command sets the deassertion hysteresis for the RMS
current of the 3rd circuit breaker to 1A.
config:# sensor ocp 3 current hysteresis 1
Commands for Environmental Sensors
A sensor configuration command for environmental sensors begins with
sensor externalsensor.
Setting the Sensor's Upper Critical Threshold
This command syntax configures the Upper Critical threshold of a numeric
environmental sensor.