Installation and Operation Instructions CONDENSING and NON-CONDENSING HYBRID CONTROL Now with Optional BACnet MS/TP HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY. C D ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
Raypak, Inc. Contents Hybrid Logic Overview . . . . . . . . . . . . . . . . . . 3 Modulating Logic Overview . . . . . . . . . . . . . . . 4 Staging Logic Overview . . . . . . . . . . . . . . . . . 4 Outdoor Reset Concept . . . . . . . . . . . . . . . . . . 5 TempTracker mod+ Hybrid Layout . . . . . . . . . . . 6 TempTracker mod+ Extension Layout . . . . . . . . . 7 Features . . . . . . . . . . . . . .
TempTracker mod+ Hybrid Installation and Operation Manual 3 Hybrid Logic Overview In response to new advancement in condensing boiler design and size, many applications utilize multiple condensing boilers in addition to the non-condensing boilers. That triggered Raypak's patent design of the TempTracker mod+ Hybrid . It is intended to manage the two groups of boilers to maximize system efficiency at the lowest operating cost while maintaining the desired comfort.
Raypak, Inc. Modulating Logic Overview The Modulation PID logic provides the capability of controlling multiple modulating current or voltage boilers. When heat is required, the control PID will activate the lead boiler and start its purge. See "Purge Delay" on page 33. This will be followed by the initiation of its modulation at the Ignition %. See "Ignition %" on page 41.
TempTracker mod+ Hybrid Installation and Operation Manual 5 Outdoor Reset Concept The TempTracker mod+ Hybrid also controls the system circulating pump with an adjustable Outdoor Cutoff. When the outdoor temperature is above the Outdoor Cutoff, the pump is off and no heating water is circulated through the system. When the outdoor temperature drops below the Outdoor Cutoff, the system pump relay is activated and the heating water circulates through the system.
Raypak, Inc. TempTracker mod+ Hybrid Layout Program Switch to restrict access to function changes. This switch is covered with Wiring Enclosure. The digital display shows the system status, set point, lead stage , and status of each stage. To view and adjust settings, press the appropriate buttons. Buttons function is presented on Bottom Row of display. LED indicates the associated relay status.
TempTracker mod+ Hybrid Installation and Operation Manual 7 TempTracker mod+ Extension Layout Extension Selection Switch to determine Stage letters and LED colors. Ext-A Stages E - J and all LEDs are Green Ext-B Stages K - P and all LEDs are Red This switch is covered with the Wiring Enclosure. LED indicates the associated relay status.
Raypak, Inc. Features The TempTracker mod+ Hybrid has been designed with Hydronic building heating, using both condensing and non-condensing boilers, as the primary purpose. As well, it is capable of controlling modulating or staging boilers. With this in mind, many of the TempTracker mod+ Hybrid features can be utilized to ease, enhance, and improve your system performance. Condensing and Non-Condensing Boilers Can be Modulating or Multi-Stage.
TempTracker mod+ Hybrid Installation and Operation Manual 9 Setback or Day/Night Scheduling Two Setback modes are available for the TempTracker mod+ Hybrid: • The Day/Night Scheduling provides an adjustable time-based schedule for the Setback (only available when Shutdown or Tstat is selected as the Setback/Shutdown Startup option). See "Shutdown/Tstat/Setback Mode" on page 26.
Raypak, Inc. Installation Each of the TempTracker mod+ Hybrid or Extension consists of three primary enclosure components. • The Enclosure Display Module: contains the control electronic board, display, buttons, LEDs and electric wiring terminals. It has two screws to hold it to the base. A program configuration switch, used to adjust the control settings, is placed above the terminals. This switch is enclosed with the enclosure wiring cover for security.
TempTracker mod+ Hybrid Installation and Operation Manual Install the Sensors 11 Immersion Heating System Sensor Immersion Well 3/8" ID 1/2" NPT Common Supply Pipe System Sensor Installation • Only use the System sensor (#012187F) provided with the unit. • The sensor wires can be extended up to 500' using a shielded 2-conductor cable (Belden #8760 or equivalent). Do not ground the shield at the sensor but at the panel using one of the terminals marked with an “O”.
MANAGEMENT EQUIPMENT 99RA Raypak, Inc. L N 1 2 HYBRID • All wiring must enter the enclosure through the bottom knockouts. • Class 1 voltage wiring must utilize a different knockout and conduit from any Class 2 voltage wiring.
SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A TempTracker mod+ Hybrid Installation and Operation Manual B 13 INPUT RATINGS: 115VAC 60Hz , 30VA MAX C USE COPPER WIRE, CLASS 1 WIRE ONLY. • The System Output relay will remain active until the System Run-On Delay expires and then it will turn off. D a Setback signal using these • When Setback is selected in the Startup, a BMS/EMS or external clock can provide input terminals.
ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK O More than one disco to de-energize the eq 99RA Raypak, Inc. Wiring the Boilers SYS PWR • When wiring Condensing and Non-Condensing boilers make sure that Condensing boilers utilize the first stages N LSYSTEM SYSTEM RATINGS: OUTPUT RATINGS:had two Condensing and Non-Condensing boilers will utilize the following stages.
ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing. 99RA TempTracker mod+ Hybrid Installation and Operation Manual 15 PROGRAM Wiring the 4-20mA Modulating Boilers SYS PWR A A D C B CUR / VLT CUR / VLT CUR (A Terminals 13, 14), (B Terminals 16, 17),... L N 3 4 5 6 7 8 9 10 11 12 2 • The TempTracker mod+ Hybrid can operate up to four 4-20 mA modulating 1motors.
HYBRID ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: Risk of More than one disconnect s to de-energize the equipme 99RA Raypak, Inc. Connecting to the Extensions and 4-20mA EMS Interface E K F L PWR NoteL Ext A Ext B E K G M H N I O J P F L G M H N I O CUR / VLT CUR / VLT CUR / VLT CUR / VLT CUR / V N GND 2 3 4 and 5 6switch 7 8 9the 10 11 11 12 B To set the Extension to a specific letter, remove the1 wiring cover Ext12A/Ext to the desired letter.
TempTracker mod+ Hybrid Installation and Operation Manual 17 Connecting to BACnet Interface Module • The TempTracker mod+ Hybrid can communicate to BACnet MSTP networks when used the BACnet Interface Module (#651735). The module must be purchased separately. • The BACnet Interface Module comes with an RJ45 cable. • Both the TempTracker mod+ Hybrid and the BACnet Interface Module (#651735) are equipped with a RJ45 socket (RS485) to connect to communicate to each other.
Raypak, Inc. -EMS 20ma -- ARE YOU SURE? -No Yes BACK ▲ ▼ SAVE Page 21 -EMS 4ma SETPOINT 70 oF [ ] BACK ▲ ▼ SAVE SETPOINT- 220 oF [ ] BACK ▲ ▼ SAVE Page 22 --- SWITCH DELAY Page 21 --- SWITCH --- 0.
TempTracker mod+ Hybrid Installation and Operation Manual 19 Page 21 -EMS 4ma - EMS INPUT MODE Disable Enable BACK ▲ ▼ SAVE Page 20 -- SENSOR TYPE Reset oF Reset oC Set Point oF Set Point oC -- BACK ▲ ▼ SAVE Disable 20ma SETPOINT220 oF [ ] BACK ▲ ▼ SAVE Modulation Page 24 -- BOILER NUMBER Staging -- 2 [ ] BACK ▲ ▼ SAVE Note To be able to change the TempTracker mod+ Hybrid settings the Program/Run Switch must be set to Program.
115VAC 60Hz , 30VA MAX C USE COPPER WIRE, CLASS 1 WIRE ONLY. 20 Raypak, Inc. D Startup Settings ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing. 99RA Program Change Switch Setting To be able to change the TempTracker mod+ Hybrid settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security.
TempTracker mod+ Hybrid Installation and Operation Manual EMS 4mA and 20mA Set Points 4mA: can be set from 50°F/ 10°C to 200°F/93°C Default: 70°F/ 21°C 20mA: can be set from 70°F/ 21°C to 220°F/104°C Default: 220°F/ 104°C Button: MENU//..../Sensor Type / EMS Input Mode/EMS 4mA Set Point • With the use of the 4-20mA EMS Interface (#012019), the TempTracker mod+ Hybrid will be able to receive a 4-20mA signal as a set point from a BMS or an EMS system as the target set point.
Raypak, Inc. Switch Delay Adjustable from 0.0 to 12.0 Hours Default: 0.5 hours Button: MENU//..../Switch Setpoint/Switch Diff/Switch Delay • The Switch Delay is an additional layer of assurance used to reduce the intermittent change of the lead group. • To switch the lead group when the temperature is dropping, the sensor temperature must remain below the Switch Set Point less the Switch Differential for the complete Switch Delay period before the switching of the lead group. • I.e.
TempTracker mod+ Hybrid Installation and Operation Manual Modulating Output Type 4-20mA, 0-10V, 1-10V (Custom) Outputs Default: 1-10v Custom Button: MENU//..../Condensing Boiler Number/Output A Type • If either of the Condensing or Non-Condensing Boiler groups was set to Modulating as the Boiler Type, the TempTracker mod+ Hybrid will offer the capability of controlling a variety of modulating signals. Each boiler can be configured to have a different modulating signal.
Raypak, Inc. Staging Mode Lo/Hi/Lo/Hi, Lo/Lo/Hi/Hi Default: Lo/Hi/Lo/Hi Button: MENU//..../Non-Condensing Output Type/Non-Cond Staging Mode • During low load conditions, some boilers run more efficient when the lower stages are energized alone than with the higher stages. For these types of boilers select Lo/Lo/Hi/Hi. Then, the TempTracker mod+ Hybrid will sequence the lower stages of all boilers set to Auto before sequencing the higher stages.
TempTracker mod+ Hybrid Installation and Operation Manual Staging Boiler Settings Staging Output Type On/Off, 2-Stage, 3-Stage, 4-Stage Outputs Default: On/Off Button: MENU//..../Output Type • The TempTracker mod+ Hybrid can sequence any type of multi-stage boiler starting with a single On/Off and up to a four 4-stages. Just select the number of stages per boiler from this menu option. • Each boiler must be connected to one of the relay outputs.
Raypak, Inc. Indirect Domestic Hot Water Set Point (Available with any of the DHW Priority options) Adjustable from 140°F/60°C to 200°F/93°C Default: 180°F/82°C Button: MENU//..../Prove-Setpoint • On a DHW call, the TempTracker mod+ Hybrid will raise the target temperature to the DHW Set Point until the DHW call expires. Shutdown/Tstat/Setback Mode Shutdown Input, Tstate Input, Setback Input Default: Shutdown Input Button: MENU//....
TempTracker mod+ Hybrid Installation and Operation Manual 27 BACnet MSTP Startup Menu -------- SETTINGS ---Season Winter System Target 140oF BACK ▲ ▼ SELECT ---- BACNET ID 477000 ---- [ ] BACK ▲ ▼ SAVE -- ARE YOU SURE? -No Yes BACK ▲ ▼ SAVE ----MS/TP ADDRESS---- 64 [ ] BACK ▲ ▼ SAVE --- BACNET MODE --Disable Enable BACK ▲ ▼ SAVE - BACNET BAUDRATE 9600 19200 38400 BACK ▲ ▼ SAVE When using the TempTracker mo
Raypak, Inc. HYBRID Operating Menu OD= 55oF SYS=143oF <> 67% B 22% STAGE ◄ ► MENU ------- SETBACK ------10 oF [ ] BACK ▲ ▼ SAVE --- PURGE DELAY 1.0 --- min [ ] BACK ▲ ▼ SAVE -- SYSTEM 10 RUN-ON -- min [ ] BACK ▲ ▼ SAVE -------- SETTINGS ---Season Winter o System Target 140 F BACK ▲ ▼ SELECT ----- SETTINGS 1 ---Setback 10oF Purge Delay 1.
TempTracker mod+ Hybrid Installation and Operation Manual 29 Modulating and Staging Operating Menu 55oF OD= SYS=143oF 67% B 22% STAGE ◄ ► MENU -------- SETTINGS ---Season Winter o System Target 140 F BACK ▲ ▼ SELECT ----- SEASON Winter Summer ----- BACK ▲ ▼ SAVE Set Point ----- SET POINT ----- 0 oF [ ] BACK ▲ ▼ SAVE SETBACK ------10 oF [ ] BACK ▲ ▼ SAVE --- PURGE DELAY 1.
Raypak, Inc. Setting the Control to Factory Defaults To Reset the TempTracker mod+ Hybrid control to its original factory defaults, power down the control. Hold down the two right most buttons while powering the control back up until the Total Clear Started screen appears. The Display will direct you to the Startup menu to program the control after the defaults are loaded.
D TempTracker mod+ Hybrid Installation and Operation Manual ENCLOSED ENERGY MANAGEMENT EQUIPMENT Operating Settings 99RA CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing. Program Change Switch Setting PROGRAM To be able to change the TempTracker mod+ Hybrid settings, the Program/Run Switch must be D C B A security. PWR Wiring SYS set to Program.
Raypak, Inc. • If required: Adjust the Water Offset in mild weather. If the ambient building temperatures are too warm in mild weather, decrease the offset. If the ambient building temperatures are too cold in mild weather, increase the Water Offset. • The rule of thumb for baseboard radiation is to change the offset 4°F for every 1°F you wish to change the building temperature. In radiant heat applications, change the offset 1F° or 2F° for every 1F° you wish to change the building temperature.
TempTracker mod+ Hybrid Installation and Operation Manual System Settings Button: MENU/ RATINGS: Settings 1 and Settings 2 menus provide access to adjusting andOUTPUT fine-tuning the system for 120VAC, 6A RESISTIVE enhanced comfort and better fuel savings. The TempTracker mod+1AHybrid behaves differently PILOT DUTY, 15A TOTAL based on the selected modes. See "Startup Settings" on page 20.
Raypak, Inc. • The System Run-On time should be set based on the size and type of the boilers and pumps used. In general, when setting the System Run-On consult the boiler and pump manufacturers for the best setting. • When the System relay is in the Run-On period, the Message Display Line will indicate that status and the remaining time.
TempTracker mod+ Hybrid Installation and Operation Manual 35 Modulating Boiler Operating Settings Gain Adjustable from -10 to +10 Default: 0 Button: MENU////Gain • The Gain adjusts the aggressiveness of the modulating PID logic. It controls how much modulation is changed when the system temperature is different from the Set Point. • A Gain of 0 is a good starting point for all systems.
Raypak, Inc. Staging Boiler Operating Settings Reaction Time Adjustable from 1 to 10 minutes Default: 2 minutes Button: MENU////Reaction Time • It is the amount of time it takes a single stage to affect the system. • After the control turns on a stage trying to meet the set point, it will not turn on another stage until the Reaction Time has elapsed. • To determine the optimum time, start with a hot system.
TempTracker mod+ Hybrid Installation and Operation Manual Day / Night Schedule 37 DAY/NIGHT SCHEDULE Set Time **:** Day Schedule 6:00a Night Schedule 8:00p Day/Night Schedules (Available when "Shutdown or Tstat" is selected from the Shutdown/Tstat/ Setback Startup menu option only) BACK ▲ ▼ SAVE Button: MENU///Day/Night Schedule • The TempTracker mod+ Hybrid has two levels of heat.
Raypak, Inc. Output Modulation Trim (Available for modulating boilers only) Adjustable from -1.0 to +1.0 Default: 0.0 Button: MENU//Output Trim • Each of the modulating stages controlled has a separate Output Trim setting. • Output Trim acts as an adjustment to a stage output percent to match the burner motor. • After adjusting the Output Trim, test the operation to make sure the results match your expectation. -- STAGE A TRIM --Output Trim +0.
TempTracker mod+ Hybrid Installation and Operation Manual 39 Boiler Stage Menu OD= 55oF SYS=143oF <> 67% B 20% STAGE ◄ ► Staging STAGE A SETTINGS Mode Auto BACK ▲ ▼ SELECT STAGE A MODE Auto Standby Manual Off On BACK ▲ ▼ SAVE MENU Modulation STAGE A SETTINGS Mode Auto Ignition % 1% Mod Start % 80% Copy Settings BACK ▲ ▼ SELECT [ STAGE A IGNITION POINT - 1% ] BACK ▲ ▼ SAVE STAGE A MODULATION START [ 75% ] B
Raypak, Inc. Display Messages The TempTracker mod+ Hybrid display layout reserved the second line for message indications. The following is a list of the most common Message Display Line information: • Boost To 170˚F The Boost has started 30 minutes before the Day Schedule setting and the Boost temperature is 170˚F. See "Boost Mode" on page 26. • DHW Call (180˚F) There is an indirect DHW call. The TempTracker mod+ Hybrid will raise the system Set Point to the indicated temperature.
TempTracker mod+ Hybrid Installation and Operation Manual 41 Mode STAGE A MODE Auto, Standby, Manual, Off, On Default: Auto Auto Standby Button: STAGE/Mode Manual • The TempTracker mod+ Hybrid only controls the modulation of boilers set to Auto or Off (after a delay) those set to Standby. None of the other settings is recommended for outputs On connected to active boilers. BACK ▲ ▼ SAVE • Any stage without an active boiler or stage connected must be set to Off.
Raypak, Inc. Copy Settings - Boiler A Only (Modulating Boilers Only) Button: STAGE/Copy Settings • If all the active modulating boilers are to be set to the same Ignition % and Modulation %, they can be set for Boiler A and then copied to the other modulating boilers. • It is still required to select the Mode for all other boilers as the Mode is NOT copied. -- COPY SETTINGS -From Stage A to all other stages BACK COPY Note The Mode MUST be set for each boiler.
TempTracker mod+ Hybrid Installation and Operation Manual Boilers are Short-Cycling • Lag Delay - Increase the Lag Delay only if modulating boilers tend to short-cycle. • Minimum Runtime - Increase the Minimum Runtime only if staging boilers tend to short-cycle. • Last Stage Hold - Increase the Last Stage Hold only if the lead boiler tends to short-cycle. System is Overshooting or Undershooting Modulating Boilers • Gain - If when using modulating boilers the system is overshooting reduce the Gain.
Object ID Device Object Device Object Device Object 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 Hybrid Reset Model Serial Number Version Operation Mode Outdoor Temperature System Temperature Output Status Control Status Season Reset Ratio Offset Outdoor Cutoff Min Water Temp Max Water Temp Setback Purge Delay System Runon Rotation Time Standby Time Last Stage Hold Con Lead St
300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 System Temperature Output Status Control Status Season Reset Ratio Offset Outdoor Cutoff Min Water Temp Max Water Temp Setback Purge Delay System Runon Rotation Time Standby Time Last Stage Hold Con Lead Stage None Con Lead Stage Gain Lag Delay Soft off Set Time Day Schedule Night Schedule HTC# 059105-00D 200 Outdoor Temperature ANALOG-VALUE ANALOG-VAL
2200 2300 2400 Day Schedule Night Schedule 1800 Con Lead Stage 2100 1700 Last Stage Hold Set Time 1600 Standby Time Min Run Time 1500 Rotation Time 1900 1400 System Runon 2000 1300 Purge Delay Non-Con Lead Stage 1200 Setback Reaction Time 1100 700 Reset Ratio 1000 600 Season Max Water Temp 500 Control Status Min Water Temp 400 Output Status 800 300 System Temperature 900 200 Outdoor Temperature Outdoor Cutoff 100 Operation Mode Offset Device Object Device Obj
MULTISTATE-VALUE MULTISTATE-VALUE 100 200 300 400 500 Operation Mode Outdoor Temperature System Temperature Output Status Control Status 2100 2200 Night Schedule HTC# 059105-00D 2000 1600 Non-Con Lead Stage Day Schedule 1500 Con Lead Stage Set Time 1400 Last Stage Hold 1900 1300 Standby Time Soft off MULTISTATE-VALUE 1200 Rotation Time 1700 1100 System Runon 1800 1000 Purge Delay Gain 900 Setback Lag Delay MULTISTATE-VALUE 800 Outdoor Cutoff ANALOG-VALUE ANALOG-
MULTISTATE-VALUE 2100 Night Schedule ANALOG-VALUE 1900 2000 Set Time Day Schedule ANALOG-VALUE 1800 Min Run Time MULTISTATE-VALUE ANALOG-VALUE ANALOG-VALUE ANALOG-VALUE 1600 1700 Non-Con Lead Stage MULTISTATE-VALUE ANALOG-VALUE ANALOG-VALUE ANALOG-VALUE Reaction Time 1500 Con Lead Stage ANALOG-VALUE 1300 1400 Standby Time 1100 1200 System Runon Rotation Time Last Stage Hold ANALOG-VALUE 1000 Purge Delay ANALOG-VALUE ANALOG-VALUE 800 900 Outdoor Cutoff ANALOG-VALUE S
TempTracker mod+ Hybrid Installation and Operation Manual 49 BACnet PICS Statement Product Model Number Protocol Revision Software Version Firmware Version TempTracker mod+ Hybrid BACnet Control Varies 1.5 2.0 2.0 Vendor Vendor ID Address and Phone Raypak, Inc. 477 2151 Eastman Ave., Oxnard, CA 93030 - (805)278-5300 Product Description TempTracker mod+ Hybrid control for hot water heating applications. (see http://www.raypak.
Raypak, Inc. Piping and Wiring Diagrams Hybrid Piping Diagram Outdoor Sensor Two Modulating Condensing Boilers and Two 4-Stage NonCondensing Boilers HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY. C D ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
TempTracker mod+ Hybrid Installation and Operation Manual 51 Hybrid Wiring Diagram Two 4-20mA Modulating Condensing Boilers and Two 4-Stage NonCondensing Boilers HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY.
Raypak, Inc. Modulating Piping Diagram Outdoor Sensor Four Modulating Boilers Startup Settings Boiler Type = Modulation Boiler Number = 4 HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: B 115VAC 60Hz , 30VA MAX C USE COPPER WIRE, CLASS 1 WIRE ONLY. D ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
TempTracker mod+ Hybrid Installation and Operation Manual 53 Modulating Wiring Diagram Four 4-20mA Modulating Boilers HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY. C D More than one disconnect switch may be required to de-energize the equipment before servicing.
Raypak, Inc. Staging Piping Diagram Outdoor Sensor Two 2-Stage Boilers HYBRID SYSTEM OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY. C D ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de-energize the equipment before servicing.
TempTracker mod+ Hybrid Installation and Operation Manual 55 Staging Wiring Diagram Two 2-Stage Boilers HYBRID SYSTEM 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS A INPUT RATINGS: 115VAC 60Hz , 30VA MAX B USE COPPER WIRE, CLASS 1 WIRE ONLY.
Specifications Voltage Input: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 VAC 60 Hz Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 VA Max Operating Temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .