Finned copper tube gas boilers & water heaters – Control manual
Configuring for DHW applications
5
SCALD HAZARD — Water over 125°F can
cause severe burns or death.
Provide temperature regulating, anti-scald devices in DHW
supply piping to xtures to prevent possibility of severe injury
or death due to scalding.
DHW options
e HeatNet control allows four options for providing DHW
heating. ese are:
Method 1 A tank-temperature sensor, connected to
the DHW Sensor input allows direct control of tank tem-
perature. Method 1 can be used for combined space heat-
ing/DHW systems.
is control method is designed to limit tank temperature
to a specied maximum. It can cause short cycling in some
cases. If the tank temperature can be allowed to vary above
and below a setpoint temperature and the application is
DHW heating only, you can use method 3 instead.
Method 2 A tank temperature aquastat in the tank
turns one boiler on and o on demand. Method 2 can be
used on combined space heating/DHW systems.
Method 3 A tank-temperature sensor, connected to
the Header sensor input of the master boiler allows direct
control of the tank temperature. e ring and sequencing
of boilers operates just as when used space heating applica-
tions. is method is limited to dedicated DHW systems.
Method 4 — 4–20 ma remote controller. is can be ap-
plied for a single boiler (or single member boilers) or for all
boilers of a network.