Finned copper tube gas boilers & water heaters – Control manual
Table 7 SETUP menus (continued) (see Table 9, page 35 for explanations)
Level 1
next item
to select
Level 2
next item
to select
back one level
Level 3
next item
to select
back one level
Default {Range}
to change value
to accept value and return to previous menu level
Typical line
(Display shows four lines at a
time; cursor indicates active
line)
PUMP OPTIONS SYSTEM PUMP POST PRG TIME 2 minutes {1 to 60 minutes}
POST PRG TIME 2M
ALWAYS ENABLED OFF
SUMMER PUMP JOG:OFF
OVR ENAB IN WWS:OFF
ALWAYS ENABLED OFF {ON or OFF}
SUMMER PUMP JOG: OFF {Day of week, MON , TUE, etc.}
OVR ENAB IN WWS OFF {ON or OFF}
LOCAL PUMP DELTA TEMP ENAB OFF {ON or OFF}
DELTA TEMP ENAB OFF
DELTA TEMP 10°
POST PRG TIME 2M
ALWAYS ENABLED OFF
DELTA TEMP 10°F {0 to 50°F}
POST PRGE TIME 2 minutes {1 to 60 minutes}
ALWAYS ENABLED OFF {ON or OFF}
PUMP/VALVE OPTION MASTER PUMP/VALVE
REMAINS ON:
OFF {ON or OFF}
MASTER PUMP/VALVE
REMAINS ON: OFF
FLOW PROVE: 10 seconds {10 to 240 seconds)
FLOW PROVE: 10S
NIGHT SETBACK SETBACK ENTRY 1 {1 through 4}
SETBACK ENTRY 1
ENTRY IS OFF
SETBACK 20°F
SETBACK TIME
ENTRY IS OFF {ON of OFF}
SETBACK 20 °F {0 to 50°F}
SETBACK TIME START DAY MON {SUN, MON, TUE, WED, THU, FRI, SAT}
START DAY MON
TIME 10:00 PM
END DAY FRI
TIME 9:00 PM
TIME 12:00 AM {Time, AM or PM}
END DAY MON {SUN, MON, TUE, WED, THU, FRI, SAT}
TIME 12:00 AM {Time, AM or PM}
OPTIONS TEMP SCALE °F {°F or °C}
TEMP SCALE °F
KEY CLICK ON
SKIP PASSW ON
BRIGHTNESS 50%
KEY CLICK ON {ON or OFF}
SKIP PASSWORD ON {ON or OFF}
BRIGHTNESS 50% {12, 25, 37, 50, 62, 75, 87, 100%}
LOG/RUNTIME RUN HOURS Total time gas valve has been open
RUN HOURS 1240
DATA LOG ENTRY 327
SIZE 1000
BOILER CYCLES 5021
DATA LOG ENTRY Current entry in the log (see Table 9, page 35)
SIZE The size of the data log
BOILER CYCLES Number of times gas valve has been cycled on/off