Finned copper tube gas boilers & water heaters – Control manual
Line #4 log entriesTable 10
Troubleshooting (continued)
9
Line #4 entry Explanation
SETBACK#1 IS ACTIVE
SETBACK#2 IS ACTIVE
SETBACK#3 IS ACTIVE
SETBACK#4 IS ACTIVE
SETBACK#1 IS EXPIRED
SETBACK#2 IS EXPIRED
SETBACK#3 IS EXPIRED
SETBACK#4 IS EXPIRED
If one or more of the setbacks is enabled, these entries will occur when the setback is started or
ended.
NO LOCAL SYSTEM FLOW
NO SYSTEM FLOW
is indicates failure of ow proving (switches wired to J11A and J11B).
COMBUSTION AIR FAIL
Logs if the combustion air damper is used and does not prove across J10B DAMPER or J12B
DAMPER
SYSTEM RESET -- ---
Records the type of reset the control board experienced —
O: stack overow; U: stack underow; (both of these are soware faults)
R: reset instruction (rmware or default load)
W: Watchdog (rmware code ran erroneous code and rebooted)
P: Power-ON (Power switch toggled)
B: Brown-out (Microcontroller saw a voltagle less than 4.5 VDC)
OUTDOOR RESET
is message indicates that warm weather shutdown is in eect.
HIGH DELTA TEMP
is message occurs when the temperature across the heat exchanger is greater than 40 °F.
LOW RETURN TEMP
If the return temperature is less than 130 °F, condensation may occur.
SHUTDOWN UV TEST
Aer 24 hours of continuous operation, the ignition control module must check its UV detector. e boiler
will shutdown and restart, allowing the self-check to occur on start-up. is message indicates this sequence
has occurred.
HIGH LIMIT EXCEEDED
is indicates the limit control has exceeded it limit.
IGNITION CTRL ALARM
is indicates the ignition control module faulted while performing an ignition sequence or while monitor-
ing during ame operation.
IRI ALARM
is indicates the gas valve proving circuit detected a gas pressure problem.
DOMESTIC HOT WATER
is indicates the occurrence of a DHW call for heat from a DHW sensor or external DHW aquastat.
LOW WATER CUT-OFF
VAR FREQ DRIVE
GAS PRESSURE
SPARE 4
OP LIMIT MECH
ese are faults due to interlocks connected to 24VAC interlock inputs on J11A and J11B.
OP LIMIT REMOTE
is indicates the soware operating temperature limit was exceeded.