Installation Guide

TABLE OF CONTENTS
Parts List 3
Conversion Instructions 4
Pre-Use Instructions 10
Lighting Instructions 12
• If the information in these instructions is not followed exactly, a fire, explosion or
production of carbon monoxide may result causing property damage, personal injury
or death.
• The qualified service agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of the converted fireplace
is checked as specified in the manufacturer’s instructions supplied with this kit.
• This conversion kit shall be installed by a qualified service agency in accordance with
Real Flame’s instructions and all applicable codes and requirements of the authority
having jurisdiction.
Type of Gas: natural gas (NG)
Normal Hourly Input: 50,000 BTUs/hr (14.65 kW)
Manifold Pressure: 7.0” water column (1.74 kPa)
Minimum Inlet Pressure: 3.5” water column (0.87 kPa)
Maximum Inlet Pressure: 10.5” water column (2.61 kPa)
This fireplace was converted on _________________
(DD/MM/YY)
to natural gas with kit no._______________________
(Found on box.)
by___________________________________________,
(Name and address of organization making this conversion.)
which accepts the responsibility that this conversion has
been properly made.
Notes: _______________________________________________
2
NOTE: In addition to these instructions, read and understand all warnings included
with the fireplace owners manual.
!
WARNING
SPECIFICATIONS