Residential Solar Plan Set Permit Package Example

OWNER BUILDER
DRAFTED BY:
CHECK BY:
DRAFTED:
B.S.
C.G.
2/9/18
SHEET:
10.44 kWDC
Photovoltaic
System
RESIDENCE
PV: 1.1
GENERAL NOTES:
-UL LISTED PRODUCTS: PHOTOVOLTAIC SOLAR MODULES UL 1703, INVERTERS UL 1741
-PHOTOVOLTAIC MODULE ARE TO BE CONSIDERED NON-COMBUSTIBLE
-ALL EXTERIOR CONDUIT IS TO BE PAINTED TO MATCH THE BUILDING IN WHICH THE CONDUIT IS ATTACHED
-ALL CONSTRUCTION SHALL COMPLY WITH THE 2016 EDITIONS OF CALIFORNIA BUILDING CODE, CALIFORNIA ELECTRICAL CODE, CALIFORNIA MECHANICAL CODE, CALIFORNIA PLUMBING CODE, CALIFORNIA FIRE CODE,
AND CALIFORNIA ENERGY CODE. LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION
-ALL MODULES AND RACKING GROUNDING LUGS SHALL BE UL 467 APPROVED (ILSCO GBL-4DBT)
-NO SHEET METAL OR TECH SCREWS SHALL BE USED TO GROUND DISCONNECT ENCLOSURE WITH TIN-PLATED ALUMINUM LUGS, PROPER GROUNDING/GROUND BAR KITS WILL BE USED
-FERROUS METAL RACEWAYS ENCLOSING GEC CONDUCTORS SHALL BE ELECTRICALLY CONTINUOUS OR BONDED IN ACCORDANCE WITH ART 250.64
-THE CONTRACTOR SHALL PROVIDE A WRITTEN LETTER TO THE BUILDING INSPECTOR IF REQUESTED, STATING THAT ALL INACCESSIBLE STRUCTURAL CONNECTIONS HAVE BEEN INSTALLED IN CONFORMATION WITH THE
REQUIREMENTS OR THE APPROVED PLANS
-APPLICATIONS FOR WHICH NO PERMIT IS ISSUED WITHIN 180 DAYS FOLLOWING THE DATE OF APPLICATION SHALL AUTOMATICALLY EXPIRE
-THIS PERMIT ISSUED SHALL BECOME INVALID UNLESS WORK AUTHORIZED IS COMMENCED WITHIN 180 DAYS, A SUCCESSFUL INSPECTION IS NOT OBTAINED IN 180 DAYS, OR IF WORK IS SUSPENDED OR ABANDON FOR
A PERIOD OF 180 DAYS, PERMITS WHICH HAVE BECOME INVALID SHALL BE A RENEWAL FEE OF 50% OF THE ORIGINAL PERMIT FEE AMOUNT WHEN THE PERMIT HAS BEEN EXPIRED FOR UP TO 1 YEAR. WHEN A PERMIT
HAS BEEN EXPIRED FOR A PERIOD IN EXCESS OF 1 YEAR, THE RENEWAL FEE SHALL BE 100% OF THE ORIGINAL PERMIT FEE
-SMOKE ALARMS TO BE INSTALLED PER JURISDICTIONS REQUEST OUTSIDE EACH SEPARATE SLEEPING AREA, IN EACH ROOM FOR SLEEPING PURPOSES, IN EACH STORY, INCLUDING BASEMENT
-CARBON MONOXIDE DETECTORS TO BE INSTALLED AS COMBINATION UNITS WITH SMOKE DETECTORS IN ALL REQUIRED LOCATIONS PER JURISDICTIONS REQUEST
- THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS.
-A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
-THIS SYSTEM IS AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
ELECTRICAL NOTES:
ALL EXPOSED ARRAY WIRING SHALL BE USE2 TYPE RATED FOR (90 C) WET CONDITIONS. OTHER OUTDOOR WIRING SHALL BE COPPER THWN2 RATED FOR (90 C) APPLICATIONS IN EMT CONDUIT
ALL DC WIRING WILL BE: DC UNGROUNDED CONDUCTOR=BLACK, DC GOUNDED CONDUCTOR=WHITE
WHERE METALLIC CONDUIT CONTAINING DC CONDUCTORS IS USED INSIDE THE BUILDING, IT SHALL BE IDENTIFIED AS CAUTION: HIGH VOLTAGE DC CIRCUITEVERY 5 FEET
#10AWG SOLID BARE COPPER GROUND WILL BE USED AS AN EQUIPMENT GROUND TO CONNECT THE PV RACKING STRUCTURE WHEN NOT EXPOSED TO DAMAGE. IF EXPSED TO DAMAGE, #6AWG WILL BE USED
ALL DISCONNECT SWITCHES SHALL BE WIRED SUCH THAT THE LINE SIDE WILL HAVE LIVE CONDUCTORS WHEN THE SWITCH IS IN THE OPEN POSITION
MAKING OF THE PV SYSTEM DISCONNECTSHALL BE ACCORDANCE WITH 690.17. MARKING OF THE DC PV POWER SOURCE SHALL BE IN ACCORDANCE WITH NEC 690.53. MARKING OF THE INVERACTIVE SYSTEM
POINT OF CONNECTION SHALL BE IN ACCORDANCE WITH NEC 690.54
ALL EXTERIOR CONDUIT, FITTINGS, AND JUNCTION BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN A WET LOCATION
GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8AWG AND NO GREATER THAN #6AWG COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.
EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS IDENTIFIED ON THE MODULE AND THE MANUFACTURERS INSTALLATION INSTRUCTIONS.
EXPOSED NONCURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENT, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136 (A) REGARDLESS OF VOLTAGE
PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION 110.26 CEC.
EXAMPLE RESIDENCE
10.44 kW PHOTOVOLTAIC SYSTEM
PROJECT ADDRESS:
PROJECT SCOPE:
1. The installation consists of (36) 290 Watt solar
photovoltaic modules ground mounted and
connected to (1) inverter and related electrical
switchgear as required by applicable codes and by the
utility company.
Total Size: 10.44 kW DC
2. The system will be interconnected and will be
operated in parallel with the utility electrical grid per
the requirements of the utility and applicable codes.
SERVING UTILITY WILL BE NOTIFIED BEFORE
ACTIVATION OF PV SYSTEM.
PROJECT DIRECTORY:
SOLAR CONTRACTOR: OWNER BUILDER
EXAMPLE