Wiring Tips for Connections and Connectors

Fig. : Radox connector fully closed
Fig. : Connection of Radox connectors showing ~ mm gap
Guide to Best Practice - Connections and Connectors
Ensuring the best performance of REC Peak Energy solar panels
Connecting panels can oen be the weakest link in a solar installation. It is here where the electrical
circuit is le exposed until the connectors are correctly aached. Over time, any weakness will be
exposed by the elements. REC Peak Energy panels have been designed for easy installation and
minimal maintenance, however there are a number of factors to watch out for when installing a
system to ensure an effective and durable source of power.
Safety when working with connectors
Safety is paramount when working with electrical
connectors. Ensure these rules are followed at all times:
Do not work on live or load-carrying parts
Connections must not be disconnected under load
Protection from electric shock must be assured by
the end product and its user
Isolate the system from the grid before carrying out
any maintenance or repair work
During long-term or overnight storage, modules
must be protected against foreign materials and the
elements e.g., water, snow, dirt or other contamination
Connector types
Over the course of its lifetime, REC has used three
different types of connector on REC Peak Energy Series
solar panels. These are:
Connecting and disconnecting
All connectors must be securely joined to each other
according to the following instructions:
To connect Radox connectors:
• Hold connectors by the grip areas on connector hoods
• Slide the male plug completely into the female socket
connector. The gap le should be about  mm
• Screw the plug into the socket until the gap is closed
completely and locked. The direction in which to lock
the connector is labeled on the connector hood
• Check that the connectors have engaged properly by
gently pulling the connectors apart
Note: Do not twist the connectors further as this
can break the internal ribs in the connector cap
Table. 
The connector types found on REC Peak Energy Series panels
Connector Type Usage
Radox
• REC production until
/
• Used with H&S junction
box
Hosiden
• MC connectable type
• REC production until
/
Multi Contact MC
• REC production from
/ to present
To disconnect Radox connectors:
• Hold the connectors at the grip areas on the connector
hood and unscrew until a gap of ~  mm is visible
• Pull the plug and socket completely apart
Changes in connector type have been made as part
of continued product improvement. When connected
properly, all connector types will provide long lasting and
secure connections.