Specifications

11
AC4x2 SERIES RATINGS
MODEL INPUT OUTPUT
(240 VAC, 50 - 60 Hz) (0 - 230 VAC)
MODEL RATED INPUT NOMINAL POWER NOMINAL POWER
NUMBER HP PHASE CURRENT (KVA) CURRENT (KVA)
(NOTE 1) (AMPS) (AMPS)
(NOTE 2) (NOTE 2)
AC4x2S-0.4 1/2 1 5.0 1.2 2.2 0.9
AC4x2T-0.4 1/2 3 2.7 1.1 2.2 0.9
AC4x2S-0.75 1 1 9.0 2.2 4.0 1.6
AC4x2T-0.75 1 3 4.8 2.0 4.0 1.6
AC4x2S-1.1 1.5 1 11.6 2.8 5.2 2.1
AC4x2T-1.1 1.5 3 6.2 2.6 5.2 2.1
AC4x2S-1.5 2 1 14.9 3.6 6.8 2.7
AC4x2T-1.5 2 3 8.1 3.4 6.8 2.7
AC4x2S-2.2 3 1 20.9 5.0 9.6 3.8
AC4x2T-2.2 3 3 11.3 4.7 9.6 3.8
AC4x2T-3.7 5 3 17.7 7.4 15.2 6.1
AC4x2T-5.5 7.5 3 25.5 10.6 22.0 8.8
AC4x2T-7.5 10 3 31.8 13.2 28.0 11.2
AC4x2T-11 15 3 47.6 19.8 42.0 16.7
AC4x2T-15 20 3 61.0 25.3 54.0 21.5
AC4x2T-18.5 25 3 77.0 32.0 68.0 27.1
AC4x2T-22 30 3 90.4 37.6 80.0 31.9
NOTE 1: See Section 3.0 for model number breakdown.
NOTE 2: For 200 VAC input voltage on THREE PHASE MODELS ONLY, multiply the input and output
current ratings by 1.15 and the output voltage by 0.87.
NOTE 3: See Section 8.0 for recommended fuse type.