Minimum voltage rating of the protection device should be 250 Vac for 240/120 Vac and
240/200 Vac rated drives, and 600 Vac for 480/400 Vac and 590/480 Vac drives.
Current limiting type fuses should be used when input fusing is required. Select fuses with
low I 2 T values, rated at 200,000 AIC. Recommended fuses are Bussman type KTK-R.
Similar fuses with equivalent ratings by other manufacturers may also be acceptable.
9.0 VOLTAGE SELECTION
9.1 INPUT VOLTAGE RATINGS
AC4x1 Series drives are rated for 240/120 Vac, 50-60 Hz input. The drive will function with
input voltage of 120 Vac (+ 10%, -15%) at 48 to 62 Hz when wired for 120 Vac input, or
with input voltage of 240 Vac (+ 10%, - 15%), at 48 to 62 Hz, when wired for 240 Vac input.
AC4x2 Series drives are rated for 240/200 Vac, 50-60 Hz input. The drive will function with
input voltages of 200 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz.
AC4x4 Series drives are rated for 480/400 Vac, 50-60 Hz input. The drive will function with
input voltages of 400 to 480 Vac (+ 10%, - 15%), at 48 to 62 Hz.
AC4x5 Series drives are rated for 590/480 Vac, 50-60 Hz input. The drive will function with
input voltages of 480 to 590 Vac (+ 10%, - 15%), at 48 to 62 Hz.