11.0 AC400 POWER WIRING DIAGRAM
Warning
Do not connect incoming AC power to output terminals T1, T2, or T3. This will
result in severe damage.
INSTALL, WIRE, AND GROUND IN ACCORDANCE WITH ALL APPLICABLE
CODES.
NOTES:
1. Wire the motor for the proper voltage per the output rating of the drive. Motor wires
MUST be run in a separate steel conduit away from control wiring and incoming AC
power wiring.
2. Do not install contactors between the drive and the motor without consulting Minarik for
more information. Failure to do so may result in drive damage.
3. Remove any existing, and do not install, power factor correction capacitors between the
drive and the motor. Failure to do so will result in drive damage.
4. Use only UL and CSA listed and approved wire.
5. Minimum wire voltage ratings: 300 V for 120, 200 and 240 Vac systems, and 600 V for
400, 480, and 590 Vac systems.
6. Wire gauge must be based on a minimum of 150% of the rated output current of the drive,
and a minimum 75°C insulation rating. Use copper wire only.
7. Wire and ground in accordance with NEC or CEC, and all applicable local codes.