Specifications
40
15.2 TWO-WIRE START/STOP CONTROL
Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using
one maintained contact (such as that from a PLC) for RUN and STOP commands. Close the
contact to RUN, and open the contact to STOP. Also shown is the wiring for a 0-10 VDC or
4-20 mA speed reference signal.
NOTES:
1. Close TB-1 to TB-2 to RUN, and open to STOP.
2. Program TB-13A, 13B, or 13C to select the desired speed reference signal. Close the
selected TB-13 terminal to TB-2 to cause the drive to respond to the selected speed
reference signal. In the diagram above, TB-13A is the terminal programmed to select the
speed reference (either 0-10 VDC or 4-20 mA).
3. If the contact closure is not made between TB-13A and TB-2, the drive will default to
keypad speed control.