Specifications
46
17.0 PARAMETER MENU
Note 1: Refer to Section 18.0 - Description of Parameters.
Note 2: If line volts is set to “low” (or set to “auto” and the input voltage is low), the range
is 25 - 150%
PARAMETER MENU
PARAM. PARAMETER RANGE OF FACTORY
NUMBER NAME ADJUSTMENT DEFAULT
0 LINE VOLTS HIGH, LOW, AUTO AUTO
1 SPEED #1 MIN FRQ - MAX FRQ 20.00 Hz
2 SPEED #2 MIN FRQ - MAX FRQ 20.00 Hz
3 SPEED #3 MIN FRQ - MAX FRQ 20.00 Hz
4 SPEED #4 MIN FRQ - MAX FRQ 20.00 Hz
5 SKIP #1 .00 Hz - MAX FRQ .00 Hz
6 SKIP #2 .00 Hz - MAX FRQ .00 Hz
7 BAND WID .00 - 10.00 Hz 1.00 Hz
8 ACCEL (NOTE 1) 30.0 SEC
9 DECEL (NOTE 1) 30.0 SEC
10 MIN FRQ .00 - MAX FRQ .50 Hz
11 MAX FRQ MIN FRQ - 120.0 Hz 60.00 Hz
12 DC BRAKE (NOTE 1) .0 VDC
13 DC TIME .0 - 999.9 SEC .0 SEC
14 DYN BRAKE OFF, ON OFF
16 CURRENT 25 - 180 % (NOTE 2) 180 %