Specifications
53
NOTE 2: This parameter can be set as low as the value shown in the WITH DB column.
However, the value shown in the WITHOUT DB column is the operational limit of a drive
without dynamic braking. For example, DECEL can be set as low as 0.1 seconds on a 10
HP, 480 Vac drive without dynamic braking, but the actual minimum deceleration time
would be 0.5 seconds.
If an attempt is made to decelerate a high-inertia load too quickly, the motor will regenerate
voltage back into the drive. This will cause the DC bus voltage to rise, which can result in a
HI VOLTS fault. In order to prevent faulting, the drive will enter DECEL FREEZE, which
halts the deceleration until the DC bus voltage returns to a normal level. The drive will then
begin to decelerate again, and if necessary, will enter DECEL FREEZE repeatedly to avoid
faulting. If a very short deceleration time is programmed, DECEL FREEZE may not be able
to compensate fast enough, resulting in a HI VOLTS fault.
In applications where very short deceleration times are required on high-inertia loads,
dynamic braking may be required. Consult the factory for more information on the Dynamic
Braking option.
10 MIN FRQ (MINIMUM FREQUENCY)
This parameter defines the lower limit of the drive’s speed range. MIN FRQ is used in
conjunction with MAX FRQ (Parameter 11 below) to define the operating range of the drive.
If MIN FRQ is set to a value above 0.0 Hz, the drive will ramp up from 0.0 Hz when given a
start command. Once running, however, the drive will not operate below the MIN FRQ
setting unless the rotation is changed, or a stop command is issued and the drive is
programmed to ramp to a stop.
If the MINIMUM FREQUENCY is set to 0.0 Hz, the drive may be operated in ZERO
SPEED mode (drive is in RUN state, but there is no output to the motor). ZERO SPEED
operation can be used in applications requiring the ability to start and stop the drive using
only the selected speed reference. The drive will start when the speed reference is raised
above 0 VDC or 4 mA, and it will stop when the reference is lowered to 0 VDC or 4 mA.
Note that the drive must be initially started using one of the normal start commands (keypad
or terminal strip).