Specifications

62
A/M SPD The AUTO/MAN key is always active.
NOTE: If the drive is switched from LOCAL to REMOTE mode, speed
control will switch to AUTO. If the drive is switched from REMOTE to
LOCAL mode, speed control will switch to MANUAL mode. The
AUTO/MAN key can then be used to select the desired mode.
30 CONTROL (START/STOP CONTROL)
This parameter selects the START/STOP control source, which is either the keypad
(LOCAL), the terminal strip (REMOTE), or the serial link (SERIAL). The
LOCAL/REMOTE key on the keypad is also affected by the setting of this parameter. The
following settings are possible:
LOCAL The drive will only respond to START/STOP commands from the
keypad. The LOCAL/REMOTE key is disabled.
REMOTE The drive will only respond to START/STOP commands from the
terminal strip. The LOCAL/REMOTE key is disabled.
SERIAL The drive will only respond to START/STOP commands through the
serial link.
KEYPAD The LOCAL/REMOTE key on the keypad is enabled and is used to
toggle between LOCAL and REMOTE modes. Press the
LOCAL/REMOTE key to select the desired mode and then press the
ENTER key within three seconds.
NOTE: If LOCAL mode is selected, a jumper is required between TB-1
and TB-2 to allow the drive to START.
TB STRIP The terminal strip is used to select LOCAL or REMOTE mode. LOCAL
mode if TB-13A or TB-13C is set for LOCAL SELECT and a contact
closure is made between TB-13A or TB-13C and TB-2. If the contact
closure is not made, the drive will be in REMOTE mode.
KEYPAD 2 Acts the same as KEYPAD, but TB-1 is disabled as a STOP input when
LOCAL mode is selected. Therefore, a jumper is not required between
TB-1 and TB-2 to START in LOCAL mode.
NOTE 1: The STOP key on the keypad is always active. The STOP
input at TB-1 is always active unless CONTROL is set to KEYPAD 2
and LOCAL mode is selected.