Specifications

67
4-20 MA Selects 4-20 mA as the AUTO speed reference input (or setpoint source
in PID mode). The 4-20 mA signal is wired to TB-5B and TB-2.
SPEED#1 Selects PRESET SPEED #1 as the AUTO speed reference.
LOC SEL Selects LOCAL mode when Parameter 30 - CONTROL is set to TB
STRIP. Drive is in REMOTE mode if contact closure is not made.
DEC FREQ Decrease frequency setpoint. Used with the MOP (motor operated pot)
function. Refer to Section 14.2.6 - SPEED REFERENCE SELECTION.
48 TB13B (TB-13B INPUT FUNCTION)
This parameter is used to select the function of terminal TB-13B. Closing TB-13B to TB-2
activates the TB - 13B function. The following functions can be selected:
NONE Disables the TB-13B function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input (or setpoint source
in PID mode). The 0-10 VDC signal is wired to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input (or setpoint source
in PID mode). The 4-20 mA signal is wired to TB-5B and TB-2.
SPEED#2 Selects PRESET SPEED #2 as the AUTO speed reference.
INC FREQ Increase frequency setpoint. Used with MOP (motor operated pot)
function. Refer to Section 14.2.6 - SPEED REFERENCE SELECTION.
49 TB13C (TB-13C INPUT FUNCTION)
This parameter is used to select the function of terminal TB-13C. Closing TB-13C to TB-2
activates the TB-13C input function. The following functions can be selected:
NONE Disables the TB-13C function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input (or setpoint source
in PID mode). The 0-10 VDC signal is wired to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input (or setpoint source
in PID mode). The 4-20 mA signal is wired to TB-5B and TB-2.