Specifications

68
SPEED#3 Selects PRESET SPEED #3 as the AUTO speed reference.
LOC SEL LOCAL SELECT - Selects LOCAL mode when Parameter 30 -
CONTROL is set to TB STRIP. Drive is in REMOTE mode if contact
closure is not made.
50 TB13D (TB-13D FUNCTION)
This parameter selects the function for TB-13D.
EXT FAULT Sets TB-13D as a normally open EXTERNAL FAULT contact. Close
TB-13D to TB-2 to trip the drive into an EXTERNAL FAULT.
EXT / FAULT Sets TB-13D as a normally closed EXTERNAL FAULT contact. Open
TB-13D to TB-2 to trip the drive into an EXTERNAL FAULT.
EXT CLEAR Sets TB-13D as a normally open EXTERNAL FAULT RESET. Close
TB-13D to TB-2 to clear a fault.
NOTE: When set to EXT CLEAR, TB-13D becomes the only terminal that can be used to
clear a fault (TB-1 will not work). However, the keypad STOP key can still be used to clear
faults.
52 TB14 OUT (TB-14 OPEN COLLECTOR OUTPUT)
This parameter sets the open-collector output indication for terminal TB-14. The following
conditions can be selected: NONE, RUN, FAULT, / FAULT (INVERSE FAULT), LOCK
(FAULT LOCKOUT), @ SPEED (AT SPEED), ABOVE #3, I LIMIT (CURRENT LIMIT),
AUTO/MAN mode, FLWR PR (FOLLOWER PRESENT), and MIN/MAX (MIN/MAX
ALARM). Refer to Section 6.2.5 - AC400 STATUS OUTPUT RELAYS.
Warning
EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters are reset to
factory defaults! The drive must be reprogrammed after a RESET in order to insure
proper operation (see Parameter 65 - PROGRAM).
FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/OR
INJURY TO PERSONNEL!