If the ENTER key is pressed while PASSWORD reads 0000, the MONITOR MODE will be
entered (if Parameter 64 - MONITOR, is set to ON), which will allow the parameters to be
viewed (except for PASSWORD), but not changed. MONITOR MODE is not present in
units that have the Metasysâ software option.
NOTE 1: The factory default value is 0019.
NOTE 2: If PASSWORD is set to 0000, the function is disabled. Pressing the PROG/RUN
key will result in direct entry into the PROGRAM mode without having to enter a password.
63 SOFTWARE (SOFTWARE VERSION)
This parameter displays the software code and revision number of the control board software.
This information is useful when contacting the factory for programming or troubleshooting
assistance. This is a “view-only” parameter, and cannot be changed.
64 MONITOR (MONITOR)
This parameter is used to enable (ON) or disable (OFF) the MONITOR MODE function.
Units with the Metasysâ software option do not have this feature. The functionality is
explained below:
ON Pressing the PROG/RUN key will activate the PASSWORD prompt. If
the ENTER key is pressed while the password value reads 0000, the
MONITOR MODE is entered and parameters can be viewed (except for
PASSWORD), but not changed.
OFF Pressing the PROG/RUN key will activate the PASSWORD prompt. If
the ENTER key is pressed while the password value reads 0000, it will
be treated as in incorrect password and the display will flash ERROR:
INCORRECT, and then return to the PASSWORD prompt to allow
another attempt at entering the correct password.