Submittal Sheet
Description
Safe-T-Switch® Model SS1 is installed inline. The patented magnetic reed switch can be
installed on a slope of up to 45°. The SS1 switch cap is easily removed for cleaning and servicing
condensate drain lines.
US Patent No 10,406,570
Code Size Qty. per Case Lbs. per Case Cubic Ft per Case
97085
Safe-T-Switch SS1
24 11 1.01
Packaging
Component List: (Fig. 1)
(1) Cap/Float Subassembly (includes Stem/Wire, two Cam Locks, Cap, Float)
(2) Tee
(3) Cleanout Tool
(4) Warning Sticker (not shown)
Installation Instructions:
Notice: Failure to read and comply with all warnings, cautions and instructions prior to starting installation may cause personal injury and/or property damage and
void the warranty. Note: this device works with both 3/4" and 1" drain pipes.
For use with 1" drain pipe, add 1" x 3/4" socket couplings (not included) to the SS1 ends.
INSTRUCTIONS FOR 3/4" DRAIN PIPE
1. Disconnect power to the air conditioner (A/C) unit at the main panel. 2. Glue a ¾" stub (not included) onto drain pan outlet adapter. 3. Glue the Tee inlet onto the
¾" stub (Note that the Tee is not directional). Tee may be sloped to a maximum of 45° from pan outlet. 4. Glue the Tee outlet onto the downstream drain line. 5. Test
all drain and tting connections for plumbing leaks. 6. Wire the switch per instructions under WIRING (Fig 7). 7. Rotate the two Cam Locks to the UNLOCK position (Fig
2). Remove the Cap/Float Subassembly from the Tee. Test the switch by lifting the Float while the unit is running. If wired correctly, the A/C unit will stop. 8. Secure
the Cap/Float Subassembly (A) Place the Cap/Float Subassembly onto the Tee, then rotate the two Cam Locks to the LOCK position (Fig 3). DO NOT GLUE THE CAP/
FLOAT SUBASSEMBLY INTO THE TEE. (B) It is recommended to push the Stem to the bottom position for the most sensitive water detection (Fig 4). If sensitivity needs
to be adjusted, move the stem up or down accordingly. 9. Test switch sensitivity: Plug drain downstream from installation point and run A/C unit to ll the drain pan.
Float should rise and A/C unit should stop before pan overows. (A) If the pan overows, increase the switch sensitivity by: 1 - Shifting the entire assembly lower, or
2 - Pushing the Stem down. (B) If the unit stops too early or too frequently, reduce the switch sensitivity by: 1 -Shifting the entire assembly higher, or 2 - Pulling the Stem
up. 10. Place included Warning Sticker on a visible surface, such as air handler or condenser unit.
(Fig.2)
(Fig.3) (Fig.4) (Fig.5) (Fig.6)(Fig.1)
(1)
(2)
(3)
Cam Lock
Cap
Float
Inlet
Slide to
bottom
Outlet
Connect
to pressurizing
or vacuuming
device
Height adjustable for
sensitivity setting
Cleanout tool stores
onboard the SS1 body
Stem/Wire
PRODUCT DATA SHEET
Page 1 of 3
SAFE-T-SWITCH
®
SS1
For primary drain outlet