Installation Manual

HORIZONTAL INSTALLATION: (See Figs. 1 and 2).
1. Female Pan Outlets: Glue ¾” long end of supplied threaded male X male stub into female drain pan outlet.
2. Press switch/cap assembly firmly into top 1” opening in Tee until the rim is flush against the Tee opening.
If more sensitivity is desired, switch may be threaded out of cap. DO NOT GLUE SWITCH/CAP INTO TEE.
3. Glue 1” X ¾” bushing into remaining 1” Tee inlet.
4. Thread female end of supplied adaptor tightly onto male pan outlet or supplied male stub, ensuring it is watertight.
5. Glue bushed inlet of Tee onto other end (SLIP end) of supplied adaptor. Tee may be sloped up to 45
o
from pan
outlet. If more slope is desired, see Vertical Installation, below.
6. For plugged installation on auxiliary outlets:
a) Seat plug firmly into ¾” outlet of Tee ensuring it is watertight. DO NOT GLUE. Pipe tape may be required
to ensure seal. Ensure Tee is level or sloped downward from pan outlet.
b) Adjust float switch downward out of cap by threading counterclockwise until float stem is at inside bottom
of Tee when switch/cap is inserted to the rim
7. For inline installation, glue ¾” outlet of Tee onto drain line.
8. Wire switch as per instructions under Wiring, below.
9. Test switch by lifting float while unit is on. If wired correctly, unit will stop when float is lifted.
10. Test all drain and fitting connections for plumbing leaks.
11. Test switch sensitivity: Plug drain downstream from installation point and run unit to fill pan. Float should
rise and unit should stop before pan overflows. If pan overflows, reposition float lower by either:
a) plumbing entire assembly lower OR;
b) by threading switch assembly counterclockwise 1/8-inch away from cap/plug so that it stops unit
sooner in response to rising water in drain.
12. Affix warning sticker to air handler or condenser unit.
INSTALLATION INSTRUCTIONS
NOTICE: FAILURE TO READ AND COMPLY WITH ALL WARININGS, RECOMMENDATIONS AN
D
INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY CAUSE PERSONAL INJURY AND/O
R
PROPERTY DAMAGE AND VOID WARRANTEE.
This device must be installed in accordance with manufacturer’s instructions and all applicable
plumbing, drainage and electrical codes to ensure proper operation.
Electric shock hazard Disconnect power supply before installation to avoid injury and/or
equipment damage. For use in Class
2 circuits only - Do not use on circuits exceeding 24 volts.
CAUTION: This device will not detect clogs occurring upstream from installation point.
CAUTION: If not present, it is recommended that a fuse and time delay be installed to protect the 24-volt circuit
and to avoid rapid cycling of equipment prior to installing this product.
CAUTION: When installing this device in plugged configuration on auxiliary drain pan outlets, it is essential that
PVC plug is closed off and watertight.
CAUTION:
This product is not intended for use in the presence of corrosive or flammable liquids and vapors.
CAUTION: Refer to the a
pp
ro
p
riate HVAC e
q
ui
p
ment o
p
eratin
g
manual
p
rior to installin
g
this
p
roduct.
WARNING