Instruction Manual

1
z PROTECTS AGAINST PHASE LOSS, UNBALANCE, UNDER
VOLTAGE, AND PHASE REVERSAL
z AVAILABLE IN 230, 380, OR 480 VAC
z LOW COST
z DIN RAIL MOUNTABLE
z INRUSH UNDER VOLTAGE DELAY
DESCRIPTION
The APMR protects three phase equipment, mostly motors, from destructive
line conditions. Specifically it detects Phase Reversal, Phase Loss, Phase
Unbalance and Low Voltage. All of these conditions, except for Phase Reversal,
produce excessive heating of motor windings, causing immediate or cumulative
damage to the motor. Phase Reversal will cause a motor to operate in the reverse
intended direction, possibly damaging machinery.
There are three models available; 230 VAC, 380 VAC, and 480 VAC. The
230 VAC model is used with 208, 220, 230, and 240 VAC rated equipment. The
380 VAC model is used with 380 and 415 VAC (European) equipment. The 480
VAC model is used with 440, 460, and 480 VAC rated equipment. The
electrical connection is three wire Delta or WYE configurations (no neutral
connection required).
The output is SPDT relay and LED. The relay is typically connected in series
with a motor contactor coil to inhibit motor start or to disconnect the motor in
the presence of a fault condition. The relay automatically resets when the fault
clears. The relay is typically used in a latching configuration so the motor has
to be restarted after the fault is cleared. The LED illuminates green when all
conditions are normal - no fault. When the LED is green, the relay is energized.
When a fault occurs, the LED turns red and the relay is de-energized. If phase
loss occurs on L1 or L3 the LED turns-off and the relay is de-energized.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER:
230 VAC: 185 min to 264 max, 3 VA (Typ)Nominal is 185 to 240, 48 to 62 Hz.
380 VAC: 320 min to 457 max, 3 VA (Typ)Nominal is 320 to 415, 48 to 62 Hz.
480 VAC: 380 min to 528 max, 3 VA (Typ)Nominal is 380 to 480, 48 to 62 Hz.
2. OUTPUT: SPDT 10 A @ 240 VAC (resistive load); 1/2 HP @ 240 VAC
Response Time:
Phase Reversal: Not greater than 120 msec
Low Voltage: 0.1 to 20 sec, user adjustable
Phase Loss and Unbalance: Not greater than 100 ms
3. TEMPERATURE COEFFICIENTS:
Unbalance: ±0.5% Over temperature range
Undervoltage: ±200 PPM/°C
4. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0 to 55°C
Storage Temperature: -40 to 80°C
Operating and Storage Humidity: 85% max. relative humidity (non-
condensing) from 0°C to 50°C.
Altitude: Up to 2000 meters
5. ISOLATION BREAKDOWN RATING: 3000 V
6. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File # E137808, UL 508, CSA C22.2 No. 14
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Refer to EMC Installation Guidelines for additional information.
7. MOUNTING: Universal mounting foot for attachment to standard DIN style
mounting rails, including top hat (T) profile rail according to EN50022 - 35
X 7.5 and 35 X 15, and G profile rail according to EN50035 - G32.
8. CONNECTION: Compression type terminal block
9. CONSTRUCTION: High impact black plastic case. Installation Category II,
Pollution Degree 2.
10. WEIGHT: 7.0 oz. (0.20 Kg)
MODEL APMR - 3 PHASE FAULT DETECTION DIN RAIL MODULE
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
Enclosure class AEN 55011RF interference
Emissions to EN 50081-2
Level 3; 10 V/mENV 50204
150 KHz - 80 MHz
Level 3; 10 V/rms EN 61000-4-6RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/O EN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m EN 61000-4-3Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contact EN 61000-4-2Electrostatic discharge
200 Hz, 50% duty cycle
Immunity to EN 50082-2
900 MHz ± 5 MHz
WARNING: 3 Phase Fault Detection Modules must never be used as
“Primary” protection against hazardous operating conditions. Machinery
must first be made safe by inherent design or the installation of guards,
shields, or other devices to protect personnel in the event of a hazardous
machine condition.