5.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
SEL RST
PROGRAMMING MODE ENTRY (SEL BUTTON)
It is recommended that all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL button. If it is not accessible then it is locked by
either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST BUTTONS)
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between
Pro and the present module. The RST button is used to select the desired
module. The displayed module is entered by pressing the SEL button.
MODULE MENU (SEL BUTTON)
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL button is pressed to advance to a particular
parameter to be changed, without changing the programming of preceding
parameters. After completing a module, the display will return to Pro NO.
Programming may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST button is used to move through
the selections/values for that parameter. Pressing the
SEL button, stores and
activates the displayed selection/value. This also advances the meter to the next
parameter.
For numeric values, press the RST button to access the value. The right hand
most digit will begin to flash. Pressing the RST button again increments the
digit by one or the user can hold the RST button and the digit will automatically
scroll. The
SEL button will advance to the next digit. Pressing and holding the
SEL button will enter the value and move to the next parameter.
PROGRAMMING MODE EXIT (SEL BUTTON)
The Programming Mode is exited by pressing the SEL button with Pro NO
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module
in sequence. When programming is complete, it is recommended to record the
parameter programming and lock out parameter programming with the user
input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 2. This is useful
when encountering programming problems.
Pressing both the SEL and the RST button on power-up will also load the
factory settings and display rESEt. This allows operation in the event of a
memory failure or corrupted data.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameters Factory Setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
6.0 PROGRAMMING THE METER
Parameters
Output
Setpoint
Parameters
Signal Input
Pro
DISPLAY
MODE
Panel Key
Function
Parameters
3-dSP
Parameters
Display and Front
NO
SEL
RST
SEL SEL SEL SEL
2-SEC
1-INP
4-SPt
5-SEr
SEL
Serial
Setup
Parameters
Secondary
OVERVIEW
PROGRAMMING MENU
Indicates Program Mode Alternating Display
Factory Settings are shown.
Parameter
Selection/Value
BUTTON DISPLAY MODE OPERATION ENTERING PROGRAM MODE PROGRAMMING MODE OPERATION
SEL Index display through enabled values Press and hold for 2 seconds to activate Store selected parameter and index to next parameter
RST Resets values (MIN / MAX) or outputs
Advances through the program menu
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value
MIN
- Minimum display capture value
“1” - To the right of the display indicates setpoint 1 output activated.
“2” - To the right of the display indicates setpoint 2 output activated.
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between
the enabled display values.
N0
USrIN