Owner manual

24
REGISTER
ADDRESS
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
FREQUENTLY USED REGISTERS
40001 Input Relative Value (Hi word)
N/A N/A N/A Read Only
Process value of present input level. This value is
affected by Input Type, Resolution, Scaling, & Offset
Value. (Relative Value = Absolute Input Value + Offset
Value)
40002 Input Relative Value (Lo word)
40003 Maximum Value (Hi word)
-199999 999999 N/A Read/Write
40004 Maximum Value (Lo word)
40005 Minimum Value (Hi word)
-199999 999999 N/A Read/Write
40006 Minimum Value (Lo word)
40007 Total Value (Hi word)
-199999999 999999999 N/A Read/Write
40008 Total Value (Lo word)
40009 Setpoint 1 Value (Hi word)
-199999 999999 100 Read/Write Active List (A or B)
40010 Setpoint 1 Value (Lo word)
40011 Setpoint 2 Value (Hi word)
-199999 999999 200 Read/Write Active List (A or B)
40012 Setpoint 2 Value (Lo word)
40013 Setpoint 3 Value (Hi word)
-199999 999999 300 Read/Write Active List (A or B)
40014 Setpoint 3 Value (Lo word)
40015 Setpoint 4 Value (Hi word)
-199999 999999 400 Read/Write Active List (A or B)
40016 Setpoint 4 Value (Lo word)
40017 Setpoint 1 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write
Active List (A or B). Applicable only for Band or
Deviation Setpoint Action.
40018 Setpoint 1 Band/Dev. Value (Lo word)
40019 Setpoint 2 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write
Active List (A or B). Applicable only for Band or
Deviation Setpoint Action.
40020 Setpoint 2 Band/Dev. Value (Lo word)
40021 Setpoint 3 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write
Active List (A or B). Applicable only for Band or
Deviation Setpoint Action.
40022 Setpoint 3 Band/Dev. Value (Lo word)
40023 Setpoint 4 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write
Active List (A or B). Applicable only for Band or
Deviation Setpoint Action.
40024 Setpoint 4 Band/Dev. Value (Lo word)
40025 Setpoint Output Register (SOR) 0 15 N/A Read/Write
Status of Setpoint Outputs. Bit State: 0 = Off, 1 = On.
Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4.
Outputs can only be activated/reset with this register
when the respective bits in the Manual Mode Register
(MMR) are set.
40026 Manual Mode Register (MMR) 0 31 0 Read/Write
Bit State: 0 = Auto Mode, 1 = Manual Mode
Bit 4 = S1, Bit 3 = S2, Bit 2 = S3, Bit 1 = S4,
Bit 0 = Linear Output
40027 Reset Output Register 0 15 0 Read/Write
Bit State: 1 = Reset Output, bit is returned to zero
following reset processing; Bit 3 = S1, Bit 2 = S2,
Bit 1 = S3, Bit 0 = S4
40028 Analog Output Register (AOR) 0 4095 0 Read/Write
Linear Output Card written to only if Linear Output is in
Manual Mode.(MMR bit 0 = 1)
40029 Input Absolute Value (Hi word)
N/A N/A N/A Read Only
Gross value of present Input level. This value is
affected by Input Type, Resolution, Scaling, but not
affected by Offset Value
40030 Input Absolute Value (Lo word)
40031 Input Offset Value (Hi word)
-199999 999999 0 Read/Write
Input Offset Value plus the Input Absolute Value equals
the Relative Input Value (standard meter value).
40032 Input Offset Value (Lo word)
INPUT PARAMETERS SEE MODULE 1 FOR PARAMETER DESCRIPTIONS
40081 Input Range 0 26 10 Read/Write
0 = 250µA 5 = 250mV 11 = 100Ω 17 = TC-K 23 = RTD 385
1 = 2.5mA 6 = 2V 12 = 1KΩ 18 = TC-R 24 = RTD 392
2 = 25mA 7 = 10V 13 = 10KΩ 19 = TC-S 25 = RTD 672
3 = 250mA 8 = 25V 14 = TC-T 20 = TC-B 26 = RTD 427
4 = 2A 9 = 100V 15 = TC-E 21 = TC-N
10 = 200V 16 = TC-J 22 = TC-C
40082 Temperature Scale (TC or RTD only) 0 1 1 Read/Write 0 = °C, 1 = °F
40083 Ice Point Compensation (TC only) 0 1 1 Read/Write 0 = Off, 1 = On
40084 ADC Conversion Rate (samples/sec) 0 5 0 Read/Write 0 = 5, 1 = 10, 2 = 20, 3 = 40, 4 = 80, 5 = 160
40085 Decimal Point 0 4 2 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000, 4 = 0.0000
40086 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100
40087 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second
40088 Filter Band 0 250 10 Read/Write 1 = 1 display unit
40089 Input Scaling Points in List Function 0 1 0 Read/Write 0 = No, 1 = Yes
List A List B Input Scaling Points Parameters
40101 40201 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points
40102 40202 Reserved N/A N/A N/A N/A
40103 40203 Scaling Pt.1 Input Value (Hi word)
-199999 999999 0 Read/Write 1 = 1 in least significant digit (Input Range dependant)
40104 40204 Scaling Pt.1 Input Value (Lo word)
PAX2A MODBUS REGISTER TABLE
The below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers or Hex as long as the conversion was done
correctly. Negative numbers are represented by two’s complement.
Note 1: The PAX2A should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.