Owner manual

25
REGISTER
ADDRESS
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
40105 40205 Scaling Pt.1 Display Value (Hi word)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
40106 40206 Scaling Pt.1 Display Value (Lo word)
thru thru Scaling Pts. 2 thru 15 Values
Registers 40107-40162 and 40207-40262 hold values
for Scaling Points 2 thru 15, and follow the same
ordering as Scaling Point 1.
40163 40263 Scaling Pt.16 Input Value (Hi word)
-199999 999999 0 Read/Write 1 = 1 in least significant digit (Input Range dependant)
40164 40264 Scaling Pt.16 Input Value (Lo word)
40165 40265 Scaling Pt.16 Display Value (Hi word)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
40166 40266 Scaling Pt.16 Display Value (Lo word)
List A List B Setpoint Values
40167 40267 Setpoint 1 Value (Hi word)
-199999 999999 100 Read/Write 1 = 1 display unit (disregard decimal point)
40168 40268 Setpoint 1 Value (Lo word)
40169 40269 Setpoint 2 Value (Hi word)
-199999 999999 200 Read/Write 1 = 1 display unit (disregard decimal point)
40170 40270 Setpoint 2 Value (Lo word)
40171 40271 Setpoint 3 Value (Hi word)
-199999 999999 300 Read/Write 1 = 1 display unit (disregard decimal point)
40172 40272 Setpoint 3 Value (Lo word)
40173 40273 Setpoint 4 Value (Hi word)
-199999 999999 400 Read/Write 1 = 1 display unit (disregard decimal point)
40174 40274 Setpoint 4 Value (Lo word)
40175 40275 Setpoint 1 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
40176 40276 Setpoint 1 Band/Dev. Value (Lo word)
40177 40277 Setpoint 2 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
40178 40278 Setpoint 2 Band/Dev. Value (Lo word)
40179 40279 Setpoint 3 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
40180 40280 Setpoint 3 Band/Dev. Value (Lo word)
40181 40281 Setpoint 4 Band/Dev. Value (Hi word)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
40182 40282 Setpoint 4 Band/Dev. Value (Lo word)
USER INPUT / FUNCTION KEYS SEE MODULE 2 FOR PARAMETER DESCRIPTIONS
40301 User Input Active State 0 1 0 Read/Write 0 = Active Low, 1 = Active High
40302 User Input 1 Action 0 28 0 Read/Write
0 = NO 8 = d-tot 16 = r-HL 24 = r-4
1 = PLOC 9 = r-tot1 17 = dISP 25 = r-34
2 = rEL 10 = r-tot2 18 = d-LEV 26 = r-234
3 = d-rEL 11 = E-tot 19 = Color 27 = r-ALL
4 = d-HLd 12 = d-HI 20 = LISt 28 = Print
5 = A-HLd 13 = r-HI 21 = r-1
6 = SYNC 14 = d-Lo 22 = r-2
7 = bAt 15 = r-Lo 23 = r-3
40303 User Input 2 Action 0 28 0 Read/Write Same as User Input 1 Action
40304 User F1 Key Action 0 17 0 Read/Write
0 = NO 5 = r-HI 10 = r-1 15 = r-234
1 = rEL 6 = r-Lo 11 = r-2 16 = r-ALL
2 = d-rEL 7 = r-HL 12 = r-3 17 = Print
3 = bAt 8 = d-LEV 13 = r-4
4 = r-tot 9 = LISt 14 = r-34
40305 User F2 Key Action 0 17 0 Read/Write Same as User F1 Key Action
40306 User F1 Second Action 0 17 0 Read/Write Same as User F1 Key Action
40307 User F2 Second Action 0 17 0 Read/Write Same as User F1 Key Action
DISPLAY PARAMETERS SEE MODULE 3 FOR PARAMETER DESCRIPTIONS
40331 Line 1 Display Color 0 2 0 Read/Write 0 = Green, 1 = Red, 2 = Orange
40332 Display Intensity Level 0 4 4 Read/Write 0 = Min.(off), 4 = Max.
40333 Display Contrast Level 0 15 7 Read/Write
40334 Line 1 Display 0 8 1 Read/Write
0 = None, 1 = Input, 2 = Total, 3 = Hi, 4 = Lo, 5 = S1,
6 = S2, 7 = S3, 8 = S4
40335 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = List
40336 Units Digit 1 (Left) 0 46 0 Read/Write
0 = _ 7 = G 14 = O 21 = V 28 = 4 35 = e 42 = r
1 = A 8 = H 15 = P 22 = Y 29 = 5 36 = g 43 = u
2 = b 9 = I 16 = Q 23 = Z 30 = 6 37 = h 44 = -
3 = C 10 = J 17 = R 24 = 0 31 = 7 38 = i 45 = °
4 = d 11 = K 18 = S 25 = 1 32 = 8 39 = n 46 =
5 = E 12 = L 19 = t 26 = 2 33 = 9 40 = o
6 = F 13 = N 20 = U 27 = 3 34 = c 41 = q
40337 Units Digit 2 (Center) 0 46 0 Read/Write Same selections as Digit 1
40338 Units Digit 3 (Right) 0 46 0 Read/Write Same selections as Digit 1
40339 Line 2 Input Display Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent
40340 Line 2 Totalizer Display Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent
40341 Line 2 Maximum (Hi) Value Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent
40342 Line 2 Minimum (Lo) Value Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent
40343 Line 2 List Selection Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE
40344 Line 2 Setpoint 1 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE
40345 Line 2 S1 Band/Dev. Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE
40346 Line 2 Setpoint 2 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE
40347 Line 2 S2 Band/Dev.Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE