TROUBLESHOOTING
PROBLEM REMEDIES
No Display At Power-Up Check power level and power connections
No Display After Power-Up
Check Display Module: d-LEU, d-Cont, and LINE 1 program settings.
Program Locked-Out
Check for Active User Input, programmed for PLOC. Deactivate User Input.
Enter proper access code at COdE 0 prompt. (Universal access code = 222)
No Line 1 Display Check program settings for Line 1 Display Value Select/Enable. Confirm at least one Line 1 Display
Value is enabled (YES).
No Line 2 Display Check program settings for Line 2 Value Access. Confirm at least one Line 2 Parameter Value is enabled
in Main Display Loop (d-rEAd, d-rSt, d-Entr).
No Line 1 Units Mnemonic Display Check program settings for Line 1 Units Mnemonic(s).
Display of OLOL, ULUL, or “ . . . .” See General Meter Specifications, Display Messages.
Incorrect Input Display Value Check Input Jumper Setting, Input Level, and Input Connections.
Verify Input - Analog program settings.
Contact factory
Modules or Parameters Not Accessible Check for corresponding plug-in option card.
Verify parameter is valid in regard to previous program settings.
Error Code: ErrKEY Keypad is active at power up. Check for depressed or stuck keypad. Press any key to clear Error Code.
Error Code: EE PAr
Error Code: EE Pdn
Parameter Data Checksum Error. Press any key to clear Error Code, verify all program settings and cycle
power. Contact factory if Error Code returns at next power-up.
Error Code: ErrPro Parameter Data Validation Error. Press any key to clear Error Code, verify all program settings and cycle
power. Contact factory if Error Code returns at next power-up.
Error Code: EE CAL Calibration Data Validation Error. Contact factory.
Error Code: EE Lin Linear Output Card Data Validation Error. Press any key to clear Error Code and cycle power. If Error
Code returns at next power-up, replace Linear Option Card or contact factory.