6.8 mOdule 8 - analOg OuTpuT parameTers () Ñ
PARAMETER MENU
Enter the analog output type. For 0-20 mA or 4-20 mA
use terminals 18 and 19. For 0-10 V use terminals 16 and
17. Only one range can be used at a time.




ANALOG TYPE
ANALOG ASSIGNMENT
Enter the Display Value that corresponds to 0 mA (0-20
mA) , 4 mA (4-20 mA) or 0 VDC (0-10 VDC).


ANALOG LOW SCALE VALUE




ANALOG HIGH SCALE VALUE
ANALOG UPDATE TIME
 to 
 to 
 to 
Enter the source for the analog output to retransmit:
 = Relative (net) Input Value. The Relative Input
Value is the Absolute Input Value that includes
the Display Offset Value.
 = Absolute (gross) Input Value. The Absolute Input
Value is based on Module 1  and  entries.
 = Calculation Value
 = Totalizer Value
 = Minimum Display Value
 = Maximum Display Value
Enter the Display Value that corresponds to 20 mA (0-20
mA) , 20 mA (4-20 mA) or 10 VDC (0-10 VDC).
Enter the analog output update rate in seconds. A value
of 0.0 allows the meter to update the analog output at the
ADC Conversion Rate.
RANGE
0 to 20 mA
4 to 20 mA
0 to 10 V
SELECTION



   
    
Ñ - An analog output card must be installed in order to access this
module.