PARAMETER MENU

COUNTER C SCALE MULTIPLIER
The number of input counts is multiplied by the scale multiplier and the scale
factor to obtain the desired process value. A scale multiplier of 1 will result in
only the scale factor affecting the display. (Details on scaling calculations are
explained at the end of Module 1 section.)


COUNTER C OPERATING MODE


COUNTER C COUNT LOAD VALUE
When reset to count load action is selected, Counter C will reset to this value.

 
COUNTER C RESET POWER-UP
Counter C may be programmed to reset at each meter power-up.


COUNTER C RESET ACTION
When Counter C is reset, it returns to zero or Counter C count load value.
This reset action affects all Counter C resets, except the Setpoint Counter Auto
Reset Action in Module 6.

COUNTER C DECIMAL POSITION
This selects the decimal point position for Counter C and any setpoint value
assigned to Counter C. The selection will also affect Counter C scale factor
calculations.


COUNTER C SCALE FACTOR
The number of input counts is multiplied by the scale factor and the scale
multiplier to obtain the desired process value. A scale factor of 1.00000 will
result in the display of the actual number of input counts. For the mode of
operation, the input signal is scaled directly. For   and   modes of
operation, the math is performed on the input signals and then the result is
scaled. To achieve correct results, both Input A and Input B must provide the
same amount of pulses per unit of measurement. (Details on scaling calculations
are explained at the end of Module 1 section.)
 to 
 to 
 
 
 
Module 5 is the programming for Counter C. For maximum input frequency,
the counter operating mode should be set to  when not in use. When set to
 the remaining related parameters are not accessible. The C annunciator
indicates that Counter C is being shown in the Display Mode. An Exchange
Parameter List feature for scale factor and count load values is explained in
Module 2.
 
  
 
 
Select the operating mode for Counter C.

Does not count.
Counter C counts the incoming pulses from Counter A input as
per Counter A mode of operation. The signal is scaled only
according to Counter C parameters.
 
Counter C counts the incoming pulses from Counter A and B
inputs as per Counter A and B modes of operation. The result
is scaled only according to Counter C parameters. (Example:
If Counter A is set for Count X1 mode and Counter B is set for
Count X2 mode, then Counter C will increment by 1 for each
pulse received on Input A and increment by 2 for each pulse
received on Input B. Counter C scale settings are then applied
and the result is displayed.)
 
Counter C counts the incoming pulses from Counter A and B
inputs as per Counter A and B modes of operation and
subtracts the B counts from the A counts. The result is scaled
only according to Counter C parameters. (Example: If Counter
A is set for Count X1 mode and Counter B is set for Count X2
mode, then Counter C will increment by 1 for each pulse
received on Input A and decrement by 2 for each pulse
received on Input B. Counter C scale settings are then applied
and the result is displayed.)
Note: When using Add Ab or Sub Ab, Counter A, B and C must all be reset
at the same time for the math to be performed on the display values.

((PAXI only)
See Serial Communications for details.