DC Compressor
Position
Compressor
Starting fail error
• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM”, detection parts.
Display
code
Title Cause of error Check point & Normal condition
Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188 ±7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50MΩ )
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly
Is inverter PCB assembly normal?
No