User guide

A
A B
A
C
MIN.1,5 m MIN.1,5 m
MIN.1,5 m
MIN.0,3 m
15
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
EXTERNAL AIR INLET
It is mandatory to provide an adequate external air intake that supplies the combustion air required for the product to work properly. The
ow of air between the outside and the installation room may be direct, through an inlet in an external wall of the room; or indirect, via
air intake from adjoining rooms and connecting permanently with the installation room (see Figure 9 b). Adjoining areas may not include
sleeping areas, garages or general areas with a re hazard. During installation one must check the minimum clearances required for air
intake from outside. Take into account the presence of doors and windows that could interfere with the proper ow of air to the stove (see
diagram below).
The air intake must have a minimum total net area of 80 cm2: the surface must be increased accordingly if within the room there are other
active generators (for example: electric fan for stale air extraction, kitchen hood, other stoves, etc...), which could cause cause depression
in the room. A check must be carried out to ensure that, with all equipment on, the pressure drop between the room and the outside does
not exceed a value of 4 Pa. (also for Oyster appliances if combustion air has not been suitably ducted outside). If necessary increase the
intake section of the air inlet, which must be made at oor level and always protected with a bird-proof outer protection grid and in such
a way that it cannot be obstructed by any object.
In order to fully enhance the sealed features and heating performance of this Oyster appliance, and thus to avoid tting a free air intake
in the room, it is recommended to connect the air required for combustion directly to the external air intake through 60 mm piping
with maximum length 3 linear metres, using the
suitable “j” 48/60 adapter supplied with the
appliance; each pipe elbow must be considered as
equivalent to one linear metre.
In the event a longer connection should be
required, further extend with an 80mm smooth
pipe. In any case do not exceed 8 linear metres
of ducting (also taking into account the elbows).
In sealed stoves the connection must be sealed in
order not to aect the overall sealed features of
the system.
For stoves installed in studio ats, bedrooms and
bathrooms (where allowed), it is mandatory to
connect the combustion air outside.
FIGURE 9 A - DIRECTLY FROM OUTSIDE
FIGURE 10
FIGURE 9 B - INDIRECTLY FROM THE ADJACENT ROOM
A=AIR INLET
B=ROOM TO BE VENTILATED
C=INCREASE OF THE GAP UNDER THE DOOR